Carrier specifications 19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 130
Image 130
19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET

19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Auto Restart Option

0/1

DSABLE/ENABLE

DSABLE

 

Remote Contacts Option

0/1

DSABLE/ENABLE

DSABLE

 

Soft Stop Amps Threshold

40 to 100

%

100

 

 

 

 

 

 

Surge/Hot Gas Bypass

 

 

 

 

Surge Limit/HGBP Option

0/1

 

0

 

Select: Surge=0, HGBP=1

 

 

 

 

 

 

Min. Load Point (T1, P1)

 

 

 

 

Surge/HGBP Delta T1

0.5 to 20

ˆF

1.5

 

Surge/HGBP Delta P1

30 to 170

PSI

50

 

Full Load Point (T2, P2)

 

 

 

 

Surge/HGBP Delta T2

0.5 to 20

ˆF

10

 

Surge/HGBP Delta P2

50 to 170

PSI

85

 

Surge/HGBP Deadband

0.5 to 3

ˆF

1

 

 

 

 

 

 

Surge Protection

 

 

 

 

Surge Delta% Amps

5 to 20

%

10

 

Surge Time Period

7 to 10

MIN

8

 

 

 

 

 

 

Ice Build Control

 

 

 

 

Ice Build Option

0/1

DSABLE/ENABLE

DSABLE

 

Ice Build Termination

0 to 2

 

0

 

0=Temp, 1=Contacts, 2=Both

 

 

 

 

 

 

Ice Build Recycle

0/1

DSABLE/ENABLE

DSABLE

 

 

 

 

 

 

Refrigerant Leak Option

0/1

DSABLE/ENABLE

DSABLE

 

Refrigerant Leak Alarm mA

4 to 20

mA

20

 

 

 

 

 

 

Head Pressure Reference

 

 

 

 

Delta P at 0% (4 mA)

20 to 60

psi

25

 

Delta P at 100% (20 mA)

20 to 60

psi

35

 

Minimum Output

0 to 100

%

0

 

CL-6

Page 130
Image 130
Carrier specifications 19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET