Table 14 — 19XR Additional Data for Marine Waterboxes*

HEAT EXCHANGER

 

ENGLISH

 

 

SI

 

FRAME, PASS

Psig

Rigging Weight

Water Volume

kPa

Rigging Weight

Water Volume

(lb)

(gal)

(kg)

(L)

 

 

 

FRAME 2, 1 AND 2 PASS

150

730

84

1034

331

318

FRAME 2, 2 PASS

150

365

42

1034

166

159

FRAME 3, 1 AND 2 PASS

150

730

84

1034

331

317

FRAME 3, 2 PASS

150

365

42

1034

166

159

FRAME 4, 1 AND 3 PASS

150

1060

123

1034

481

465

FRAME 4, 2 PASS

150

530

61

1034

240

231

FRAME 5, 1 AND 3 PASS

150

1240

139

1034

562

526

FRAME 5, 2 PASS

150

620

69

1034

281

263

FRAME 6, 1 AND 3 PASS

150

1500

162

1034

680

612

FRAME 6, 2 PASS

150

750

81

1034

340

306

FRAME 7, 1 AND 3 PASS

150

2010

326

1034

912

1234

FRAME 7, 2 PASS

150

740

163

1034

336

617

FRAME 8, 1 AND 3 PASS

150

1855

406

1034

841

1537

FRAME 8, 2 PASS

150

585

203

1034

265

768

FRAME 2, 1 AND 3 PASS

300

860

84

2068

390

318

FRAME 2, 2 PASS

300

430

42

2068

195

159

FRAME 3, 1 AND 3 PASS

300

860

84

2068

390

317

FRAME 3, 2 PASS

300

430

42

2068

195

159

FRAME 4, 1 AND 3 PASS

300

1210

123

2068

549

465

FRAME 4, 2 PASS

300

600

61

2068

272

231

FRAME 5, 1 AND 3 PASS

300

1380

139

2068

626

526

FRAME 5, 2 PASS

300

690

69

2068

313

263

FRAME 6, 1 AND 3 PASS

300

1650

162

2068

748

612

FRAME 6, 2 PASS

300

825

81

2068

374

306

FRAME 7, 1 AND 3 PASS

300

3100

326

2068

1406

1234

FRAME 7, 2 PASS

300

1830

163

2068

830

617

FRAME 8, 1 AND 3 PASS

300

2745

405

2068

1245

1533

FRAME 8, 2 PASS

300

1475

203

2068

766

768

*Add to heat exchanger data for total weights or volumes.

NOTES:

1.Weight adder shown is the same for cooler and condenser of equal frame size.

2.For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volumes).

Table 15 — Compressor Weights

 

 

FRAME 2

FRAME 3

FRAME 4

FRAME 4

FRAME 5

 

 

COMPRESSOR

COMPRESSOR

 

 

COMPRESSOR

COMPRESSOR

COMPRESSOR

COMPONENT

WEIGHT (Without

WEIGHT (With

WEIGHT

WEIGHT

WEIGHT

 

 

Split Ring Diffuser)

Split Ring Diffuser)

 

 

 

 

 

 

 

 

 

 

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

SUCTION ELBOW

50

23

54

24

175

79

175

79

400

181

DISCHARGE ELBOW

60

27

46

21

157

71

157

71

325

147

TRANSMISSION*

320

145

730

331

656

298

656

298

1000

454

SUCTION HOUSING

300

136

350

159

446

202

810

367

1200

544

IMPELLER SHROUD

35

16

80

36

126

57

200

91

250

113

COMPRESSOR BASE

1260

571

1050

476

1589

721

2022

917

3695

1676

DIFFUSER

35

16

70

32

130

59

130

59

300

136

OIL PUMP

125

57

150

68

150

68

150

68

185

84

MISCELLANEOUS

100

45

135

61

144

65

200

91

220

100

TOTAL WEIGHT

2300

1043

2660

1207

3712

1684

4548

2063

6850

3107

(Less Motor and Elbows)

 

 

 

 

 

 

 

 

 

 

*Transmission weight does not include rotor, shaft, and gear.

93

Page 93
Image 93
Carrier XRV specifications 19XR Additional Data for Marine Waterboxes, Compressor Weights

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.