Carrier XRV specifications CHILLER FAMILIARIZATION and, 19XR Identification

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 5
Image 5
CHILLER FAMILIARIZATION

Factory-installed additional components are referred to as options in this manual; factory-supplied but field-installed ad- ditional components are referred to as accessories.

The chiller software part number of the 19XR unit is located on the back of the CVC/ICVC.

CHILLER FAMILIARIZATION

(Fig. 1 and 2)

Chiller Information Nameplate — The information nameplate is located on the right side of the chiller control panel.

System Components — The components include the cooler and condenser heat exchangers in separate vessels, motor-compressor, lubrication package, control panel, and mo- tor starter. All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded pipe cap during factory assembly.

Cooler — This vessel (also known as the evaporator) is lo- cated underneath the compressor. The cooler is maintained at lower temperature/pressure so evaporating refrigerant can re- move heat from water flowing through its internal tubes.

Condenser — The condenser operates at a higher temperature/pressure than the cooler and has water flowing

through its internal tubes in order to remove heat from the refrigerant.

Motor-CompressorThis component maintains sys- tem temperature and pressure differences and moves the heat- carrying refrigerant from the cooler to the condenser.

Control Panel — The control panel is the user interface for controlling the chiller. It regulates the chiller’s capacity as required to maintain proper leaving chilled water temperature. The control panel:

registers cooler, condenser, and lubricating system pressures

shows chiller operating condition and alarm shutdown conditions

records the total chiller operating hours

sequences chiller start, stop, and recycle under micropro- cessor control

displays status of motor starter

provides access to other CCN (Carrier Comfort Net- work) devices and energy management systems

Languages pre-installed at factory include: English, Chi- nese, Japanese, and Korean (ICVC only).

International language translator (ILT) is available for conversion of extended ASCII characters (ICVC only).

19XRV 52 51 473 DG H 64 –

19XR- — High Efficiency Hermetic

Centrifugal Liquid Chiller

19XRV — High Efficiency Hermetic Centrifugal Liquid Chiller with Variable Frequency Drive Unit-Mounted

Cooler Size

 

10-12 (Frame 1 XR)

55-57 (Frame 5 XR)

15-17 (Frame 1 XR)

5F (Frame 5 XR)

20-22 (Frame 2 XR)

5G (Frame 5 XR)

30-32 (Frame 3 XR)

5H (Frame 5 XR)

35-37 (Frame 3 XR)

60-62 (Frame 6 XR)

40-42 (Frame 4 XR)

65-67 (Frame 6 XR)

45-47 (Frame 4 XR)

70-72 (Frame 7 XR)

50-52 (Frame 5 XR)

75-77 (Frame 7 XR)

5A (Frame 5 XR)

80-82 (Frame 8 XR)

5B (Frame 5 XR)

85-87 (Frame 8 XR)

5C (Frame 5 XR)

 

Condenser Size

10-12 (Frame 1 XR)

15-17 (Frame 1 XR)

20-22 (Frame 2 XR)

30-32 (Frame 3 XR)

35-37 (Frame 3 XR)

40-42 (Frame 4 XR)

45-47 (Frame 4 XR)

50-52 (Frame 5 XR)

55-57 (Frame 5 XR)

60-62 (Frame 6 XR)

65-67 (Frame 6 XR)

70-72 (Frame 7 XR)

75-77 (Frame 7 XR)

80-82 (Frame 8 XR)

85-87 (Frame 8 XR)

Compressor Code

(First Digit Indicates Compressor Frame Size)*

*Second digit will be a letter (example 4G3)

on units equipped with split ring diffuser.MODEL NUMBER NOMENCLATURE

27 99 Q 59843

Special Order Indicator

– — Standard

S — Special Order

Motor Voltage Code Code Volts-Phase-Hertz

60 — 200-3-60

61 — 230-3-60

62 — 380-3-60

63 — 416-3-60

64 — 460-3-60

65 — 575-3-60

66 — 2400-3-60

67 — 3300-3-60

68 — 4160-3-60

69 — 6900-3-60

50 — 230-3-50

51 — 346-3-50

52 — 400-3-50

53 — 3000-3-50

54 — 3300-3-50

55 — 6300-3-50

Motor Efficiency Code

H — High Efficiency

S — Standard Efficiency

Motor Code

 

 

BD

CD

DB

EH

BE

CE

DC

EJ

BF

CL

DD

EK

BG

CM

DE

EL

BH

CN

DF

EM

 

CP

DG

EN

 

CQ

DH

EP

 

 

DJ

 

Week of Year

Year of Manufacture

Unique Number

Place of Manufacture

SERIAL NUMBER BREAKDOWN

Fig. 1 — 19XR Identification

5

Page 5
Image 5
Carrier XRV specifications CHILLER FAMILIARIZATION and, 19XR Identification