Carrier XRV, 19XR CVC/ICVC Primary and Secondary Messages and, I. Chiller Protect Limit Faults

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 81
Image 81

Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

I. CHILLER PROTECT LIMIT FAULTS

STATE

PRIMARY

SECONDARY

ALARM MESSAGE

ADDITIONAL

MESSAGE

MESSAGE

PRIMARY CAUSE

CAUSE/REMEDY

 

200

PROTECTIVE

1M CONTACT

200->1M Aux Contact Fault;

 

 

LIMIT

FAULT

Check 1M Contactor and

 

 

 

 

Aux

 

201

PROTECTIVE

2M CONTACT

201->2M Aux Contact Fault;

 

 

LIMIT

FAULT

Check 2M Contactor and

 

 

 

 

Aux

 

202

PROTECTIVE

MOTOR AMPS

202->Motor Amps Not

Check for wiring of current transformers to the ISM.

 

LIMIT

NOT SENSED

Sensed — Average Line

Check main circuit breaker for trip.

 

 

 

Current [VALUE]

 

203

FAILURE TO

EXCESS

203->Motor Acceleration

Check to be sure that the inlet guide vanes are closed

 

START

ACCELERATION

Fault — Average Line

at start-up.

 

 

TIME

Current [VALUE]

Check starter for proper operation.

 

 

 

 

Reduce unit pressure if possible.

204

FAILURE TO

1M/2M CONTACT

204->1M/2M Aux Contact

 

 

STOP

FAULT

Stop Fault; Check 1M/2M

 

 

 

 

Contactors and Aux

 

205

FAILURE TO

MOTOR AMPS

205->Motor Amps When

 

 

STOP

WHEN STOPPED

Stopped — Average Line

 

 

 

 

Current [VALUE]

 

206

PROTECTIVE

STARTER

206->Starter Fault Cutout;

For Benshaw Inc. RediStart MICRO™ starters, view

 

LIMIT

FAULT

Check Optional Starter

fault code at RediStart MICRO display. Press FAULT

 

 

 

Contacts

RESET to clear faults.

207

PROTECTIVE

HIGH CONDENSER

207->High Cond Pressure

Check for high condenser water temperatures, low

 

LIMIT

PRESSURE

cutout. [VALUE] exceeded

water flow, fouled tubes.

 

 

 

limit of [LIMIT]*.

Check for division plate/gasket bypass.

 

 

 

 

Check for noncondensables.

 

 

 

 

Check transducer wiring and accuracy.

 

 

 

 

If [VALUE] is less than Limit then check the

 

 

 

 

1CR Starting Circuit.

208

PROTECTIVE

EXCESSIVE

208->Compressor Motor

Check motor current for proper calibration.

 

LIMIT

MOTOR AMPS

Amps [VALUE] exceeded

Check inlet guide vane actuator.

 

 

 

limit of [LIMIT]*.

 

209

PROTECTIVE

LINE PHASE

209->Line Phase Loss;

Check transformers to ISM.

 

LIMIT

LOSS

Check ISM Fault History to

Check power distribution bus.

 

 

 

Identify Phase

Consult power company.

210

PROTECTIVE

LINE VOLTAGE

210->Single Cycle Line

 

 

LIMIT

DROPOUT

Voltage Dropout

 

211

PROTECTIVE

HIGH LINE

211->High Average Line

Check transformers to ISM.

 

LIMIT

VOLTAGE

Voltage [VALUE]

Check distribution bus.

 

 

 

 

Consult power company.

212

PROTECTIVE

LOW LINE

212->Low Average Line

Check transformers to ISM.

 

LIMIT

VOLTAGE

Voltage [VALUE]

Check distribution bus.

 

 

 

 

Consult power company.

213

PROTECTIVE

STARTER MODULE

213->Starter Module Power-

 

 

LIMIT

RESET

On Reset When Running

 

214

PROTECTIVE

POWER LOSS

214->Power Loss:

Check transformers to ISM.

 

LIMIT

 

Check voltage supply

Check distribution bus.

 

 

 

 

Consult power company.

215

PROTECTIVE

LINE CURRENT

215->Line Current

Check upstream equipment.

 

LIMIT

IMBALANCE

Imbalance; Check ISM Fault

 

 

 

 

History to Identify Phase

 

216

PROTECTIVE

LINE VOLTAGE

216->Line Voltage

Check upstream equipment.

 

LIMIT

IMBALANCE

Imbalance; Check ISM Fault

 

 

 

 

History to Identify Phase

 

217

PROTECTIVE

MOTOR OVERLOAD

217->Motor Overload Trip;

Check ISM configuration.

 

LIMIT

TRIP

Check ISM configurations

 

218

PROTECTIVE

MOTOR LOCKED

218->Motor Locked Rotor

Check ISM configuration.

 

LIMIT

ROTOR TRIP

Amps exceeded; Check

 

 

 

 

Motor & ISM Config

 

219

PROTECTIVE

STARTER LOCK

219->Starter Locked Rotor

Check ISM configuration.

 

LIMIT

ROTOR TRIP

Amps Rating exceeded

 

220

PROTECTIVE

GROUND FAULT

220->Ground Fault Trip;

 

 

LIMIT

 

Check Motor and Current

 

 

 

 

Transformers

 

221

PROTECTIVE

PHASE REVERSAL

221->Phase Reversal Trip;

 

 

LIMIT

TRIP

Check Power Supply

 

222

PROTECTIVE

LINE FREQUENCY

222->Line Frequency —

 

 

LIMIT

TRIP

[VALUE] exceeded limit of

 

 

 

 

[LIMIT]. Check Power

 

 

 

 

Supply.

 

223

PROTECTIVE

STARTER MODULE

223->Starter Module

 

 

LIMIT

FAILURE

Hardware Failure

 

81

Page 81
Image 81
Carrier XRV CVC/ICVC Primary and Secondary Messages and, Custom Alarm/Alert Messages with Troubleshooting Guides cont