Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

J. CHILLER ALERTS (cont)

STATE

PRIMARY

SECONDARY

ALARM MESSAGE

ADDITIONAL

MESSAGE

MESSAGE

PRIMARY CAUSE

CAUSE/REMEDY

 

149

SENSOR ALERT

HIGH DISCHARGE

149->Comp Discharge Temp

Check sensor resistance or voltage drop.

 

 

TEMP

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check for proper condenser flow and

 

 

 

 

temperature.

 

 

 

 

Check for high lift or low load.

 

 

 

 

Check for proper inlet guide vane and diffuser

 

 

 

 

actuator operation (Size 5 compressor Only).

 

 

 

 

Check for fouled tubes or noncondensables in

 

 

 

 

the refrigerant system.

150

SENSOR ALERT

HIGH BEARING

150->Comp Thrust Bearing

Check sensor resistance or voltage drop.

 

 

TEMPERATURE

Temp [VALUE] exceeded limit

Check for proper wiring.

 

 

 

of [LIMIT]*.

Check for partially closed service valves.

 

 

 

 

Check oil cooler TXV.

 

 

 

 

Check oil filter.

 

 

 

 

Check oil level.

151

CONDENSER

PUMP RELAY

151->High Condenser

Check sensor wiring and accuracy.

 

PRESSURE ALERT

ENERGIZED

Pressure [VALUE]: Pump

Check condenser flow and fluid

 

 

 

Energized to Reduce

temperature.

 

 

 

Pressure.

Check for fouled tubes. This alarm is not

 

 

 

 

caused by the High Pressure Switch.

152

RECYCLE

EXCESSIVE RECYCLE

152->Excessive recycle starts.

Chiller load is too low to keep compressor on

 

ALERT

STARTS

 

line and there has been more than

 

 

 

 

5 starts in 4 hours. Increase chiller load,

 

 

 

 

adjust hot gas bypass, increase RECYCLE

 

 

 

 

RESTART DELTA T from SETUP1 Screen.

153

no message:

no message;

153->Lead/Lag Disabled:

Illegal chiller address configuration in Lead/

 

ALERT only

ALERT only

Duplicate Chiller Address;

Lag screen. Both chillers require a different

 

 

 

Check Configuration

address.

154

POTENTIAL

COND PRESS/TEMP

154->Condenser freeze up

The condenser pressure transducer is read-

 

FREEZE-UP

TOO LOW

prevention

ing a pressure that could freeze the con-

 

 

 

 

denser tubes.

 

 

 

 

Check for condenser refrigerant leaks.

 

 

 

 

Check fluid temperature.

 

 

 

 

Check sensor wiring and accuracy.

 

 

 

 

Place the chiller in PUMPDOWN mode if the

 

 

 

 

vessel is evacuated.

155

OPTION SENSOR

REMOTE RESET

155->Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

SENSOR

Disabled:

Check for proper wiring.

 

 

 

Remote Reset Sensor

 

156

OPTION SENSOR

AUTO CHILLED

156->Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

WATER RESET

Disabled:

Check for proper wiring.

 

 

 

Auto Chilled Water Reset

 

157

OPTION SENSOR

AUTO DEMAND

157->Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

LIMIT INPUT

Disabled:

Check for proper wiring.

 

 

 

Auto Demand Limit Input

 

158

SENSOR ALERT

SPARE TEMPERATURE

158->Spare Temperature #1

Check sensor resistance or voltage drop.

 

 

#1

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT].*

 

159

SENSOR ALERT

SPARE TEMPERATURE

159->Spare Temperature #2

Check sensor resistance or voltage drop.

 

 

#2

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT].*

 

160

DIFFUSER

DIFFUSER

160->Diffuser Position Alert;

Check diffuser configuration in SETUP2

 

ALERT

POSITION

Check Diffuser Configuration.

screen.

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.