Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

J. CHILLER ALERTS (cont)

STATE

PRIMARY

SECONDARY

ALARM MESSAGE

ADDITIONAL

MESSAGE

MESSAGE

PRIMARY CAUSE

CAUSE/REMEDY

 

149

SENSOR ALERT

HIGH DISCHARGE

149->Comp Discharge Temp

Check sensor resistance or voltage drop.

 

 

TEMP

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check for proper condenser flow and

 

 

 

 

temperature.

 

 

 

 

Check for high lift or low load.

 

 

 

 

Check for proper inlet guide vane and diffuser

 

 

 

 

actuator operation (Size 5 compressor Only).

 

 

 

 

Check for fouled tubes or noncondensables in

 

 

 

 

the refrigerant system.

150

SENSOR ALERT

HIGH BEARING

150->Comp Thrust Bearing

Check sensor resistance or voltage drop.

 

 

TEMPERATURE

Temp [VALUE] exceeded limit

Check for proper wiring.

 

 

 

of [LIMIT]*.

Check for partially closed service valves.

 

 

 

 

Check oil cooler TXV.

 

 

 

 

Check oil filter.

 

 

 

 

Check oil level.

151

CONDENSER

PUMP RELAY

151->High Condenser

Check sensor wiring and accuracy.

 

PRESSURE ALERT

ENERGIZED

Pressure [VALUE]: Pump

Check condenser flow and fluid

 

 

 

Energized to Reduce

temperature.

 

 

 

Pressure.

Check for fouled tubes. This alarm is not

 

 

 

 

caused by the High Pressure Switch.

152

RECYCLE

EXCESSIVE RECYCLE

152->Excessive recycle starts.

Chiller load is too low to keep compressor on

 

ALERT

STARTS

 

line and there has been more than

 

 

 

 

5 starts in 4 hours. Increase chiller load,

 

 

 

 

adjust hot gas bypass, increase RECYCLE

 

 

 

 

RESTART DELTA T from SETUP1 Screen.

153

no message:

no message;

153->Lead/Lag Disabled:

Illegal chiller address configuration in Lead/

 

ALERT only

ALERT only

Duplicate Chiller Address;

Lag screen. Both chillers require a different

 

 

 

Check Configuration

address.

154

POTENTIAL

COND PRESS/TEMP

154->Condenser freeze up

The condenser pressure transducer is read-

 

FREEZE-UP

TOO LOW

prevention

ing a pressure that could freeze the con-

 

 

 

 

denser tubes.

 

 

 

 

Check for condenser refrigerant leaks.

 

 

 

 

Check fluid temperature.

 

 

 

 

Check sensor wiring and accuracy.

 

 

 

 

Place the chiller in PUMPDOWN mode if the

 

 

 

 

vessel is evacuated.

155

OPTION SENSOR

REMOTE RESET

155->Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

SENSOR

Disabled:

Check for proper wiring.

 

 

 

Remote Reset Sensor

 

156

OPTION SENSOR

AUTO CHILLED

156->Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

WATER RESET

Disabled:

Check for proper wiring.

 

 

 

Auto Chilled Water Reset

 

157

OPTION SENSOR

AUTO DEMAND

157->Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

LIMIT INPUT

Disabled:

Check for proper wiring.

 

 

 

Auto Demand Limit Input

 

158

SENSOR ALERT

SPARE TEMPERATURE

158->Spare Temperature #1

Check sensor resistance or voltage drop.

 

 

#1

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT].*

 

159

SENSOR ALERT

SPARE TEMPERATURE

159->Spare Temperature #2

Check sensor resistance or voltage drop.

 

 

#2

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT].*

 

160

DIFFUSER

DIFFUSER

160->Diffuser Position Alert;

Check diffuser configuration in SETUP2

 

ALERT

POSITION

Check Diffuser Configuration.

screen.

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

84

Page 84
Image 84
Carrier 19XR, XRV specifications Pressure Alert, Recycle, Option Sensor, Diffuser

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.