Carrier 19XR, XRV specifications Allen-Bradley Wye-Delta Unit-Mounted Starter cont

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 102
Image 102
Manual background

102

 

 

LEGEND

 

C

Contactor

LL

Control Power Supply

CB

Circuit Breaker

M

Contactor

CP

Control Power

OP

Oil Pump

CT

Current Transformer

PFCC

Power Factor Correction Capacitor

DS

Disconnect Switch

RES

Resistor

FU

Fuse

S

Contactor

GRD

Ground

ST

Shunt Trip

HPR

High Pressure Relay

TB

Terminal Block

ISM

Integrated Starter Module

TC

Transition Contactor

L

Main Supply Power

VL

Wire Label

NOTES:

1.Remote device.

2.Transformer connected for 480 v primary 120 v secondary. For other voltages see chart:

 

PRIMARY

 

SECONDARY

 

H1-H2

H1-H3

H1-H4

H1-H5

X1-X2

X1-X3

X1-X4

240

416

480

600

99

120

 

130

230

400

460

575

95

115

 

125

220

380

440

550

91

110

 

120

208

 

 

500

85

100

 

110

3.Current transformer

•amps nameplate ratio

•amps effective ratio with primary turns

•polarity marking

Be sure to connect per polarity markings.

4.“S” - “2M” contactors are electrically and mechanically interlocked.

5.Live capacitor unit. Deenergize starter. Wait one (1) minute and ground terminals before servicing.

6.All control wiring 14 gage red except as noted.

Fig. 45 — Allen-Bradley Wye-Delta Unit-Mounted Starter (cont)

Page 102
Image 102
Carrier 19XR, XRV specifications Allen-Bradley Wye-Delta Unit-Mounted Starter cont