Carrier specifications 19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 131
Image 131
19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET

CUT ALONG DOTTED LINECUT ALONG DOTTED LINE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -

19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Comp Motor Temp Override

150 to 200

DEG F

200

 

Cond Press Override

90 to 165

PSI

125

 

Comp Discharge Alert

125 to 200

DEG F

200

 

Comp Thrust Brg Alert

165 to 185

DEG F

175

 

 

 

 

 

 

Chilled Medium

0/1

WATER/BRINE

WATER

 

Chilled Water Deadband

.5 to 2.0

ˆF

1.0

 

Evap Refrig Trippoint

0.0 to 40.0

DEG F

33

 

Refrig Override Delta T

2.0 to 5.0

ˆF

3

 

Condenser Freeze Point

–20 to 35

DEG F

34

 

 

 

 

 

 

Evap Flow Delta P Cutout

0.5 to 50.0

PSI

5.0

 

Cond Flow Delta P Cutout

0.5 to 50.0

PSI

5.0

 

Water Flow Verify Time

0.5 to 5

MIN

5

 

Oil Press Verify Time

15 to 300

SEC

40

 

Recycle Control

 

 

 

 

Restart Delta T

2.0 to 10.0

DEG F

5

 

Shutdown Delta T

0.5 to 4.0

DEG F

1

 

 

 

 

 

 

SPARE ALERT/ALARM ENABLE

 

 

 

 

Disable=0, Lo=1/3, Hi=2/4

 

 

 

 

 

 

 

 

 

Spare Temp #1 Enable

0 to 4

 

0

 

Spare Temp #1 Limit

–40 to 245

DEG F

245

 

Spare Temp #2 Enable

0 to 4

 

0

 

Spare Temp #2 Limit

–40 to 245

DEG F

245

 

CL-7

Page 131
Image 131
Carrier specifications 19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET