CUT ALONG DOTTED LINECUT ALONG DOTTED LINE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -

CUT ALONG DOTTED LINECUT ALONG DOTTED LINE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -

19XR, XRV PIC II ISM_CONF TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Starter Type

0 to 2

 

1

 

(0=Full, 1=Red, 2=SS/VFD)

 

 

 

 

 

 

Motor Rated Line Voltage

200 to 13200

VOLTS

460

 

Volt Transformer Ratio: 1

1 to 35

 

1

 

Overvoltage Threshold

105 to 115

%

115

 

Undervoltage Threshold

85 to 95

%

85

 

Over/Under Volt Time

1 to 10

SEC

5

 

Voltage% Imbalance

1 to 10

%

10

 

Voltage Imbalance Time

1 to 10

SEC

5

 

Motor Rated Load Amps

10 to 5000

AMPS

200

 

Motor Locked Rotor Trip

100 to 60000

AMPS

1000

 

Locked Rotor Start Delay

1 to 10

cycles

5

 

Starter LRA Rating

100 to 60000

AMPS

2000

 

Motor Current CT Ratio: 1

3 to 1000

 

100

 

Current% Imbalance

5 to 40

%

15

 

Current Imbalance Time

1 to 10

SEC

5

 

Grnd Fault CT’s?

0/1

NO/YES

YES

 

Ground Fault CT Ratio: 1

150

 

150

 

Ground Fault Current

1 to 25

AMPS

15

 

Ground Fault Start Delay

1 to 20

cycles

10

 

Ground Fault Persistence

1 to 10

cycles

5

 

Single Cycle Dropout

0/1

DSABLE/ENABLE

DSABLE

 

Frequency-60 Hz? (No=50)

0/1

NO/YES

YES

 

Line Frequency Faulting

0/1

DSABLE/ENABLE

DSABLE

 

CL-5