Carrier specifications 19XR, XRV PIC II RAMPDEM TABLE CONFIGURATION SHEET

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 134
Image 134
19XR, XRV PIC II RAMP_DEM TABLE CONFIGURATION SHEET

19XR, XRV PIC II RAMP_DEM TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Pulldown Ramp Type:

0/1

 

1

 

Select: Temp=0, Load=1

 

 

 

 

 

 

Demand Limit + kW Ramp

 

 

 

 

Demand Limit Source

0/1

 

0

 

Select: Amps=0, kW=1

 

 

 

 

 

 

Motor Load Ramp% Min

5 to 20

 

10

 

Demand Limit Prop Band

3 to 15

%

10

 

Demand Limit At 20 mA

40 to 100

%

40

 

20 mA Demand Limit Opt

0/1

DSABLE/ENABLE

DSABLE

 

Motor Rated Kilowatts

50 to 9999

kW

145

 

Demand Watts Interval

5 to 60

MIN

15

 

19XR, XRV PIC II TEMP_CTL TABLE CONFIGURATION SHEET

 

 

 

 

 

 

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Control Point

 

 

 

 

ECW Control Option

0/1

DSABLE/ENABLE

DSABLE

 

Temp Pulldown Deg/Min

2 to 10

ˆF

3

 

 

 

 

 

 

Temperature Reset

 

 

 

 

RESET TYPE 1

 

 

 

 

Degrees Reset At 20 mA

–30 to 30

ˆF

10

 

RESET TYPE 2

 

 

 

 

Remote Temp -> No Reset

–40 to 245

DEG F

85

 

Remote Temp -> Full Reset

–40 to 245

DEG F

65

 

Degrees Reset

–30 to 30

ˆF

10

 

RESET TYPE 3

 

 

 

 

CHW Delta T -> No Reset

0 to 15

ˆF

10

 

CHW Delta T -> Full Reset

0 to 15

ˆF

0

 

Degrees Reset

–30 to 30

ˆF

5

 

 

 

 

 

 

Select/Enable Reset Type

0 to 3

 

0

 

CL-10