Carrier 19XR, XRV Chillers with Isolation Valves, Push refrigerant into the chiller condenser

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 70
Image 70

TRANSFER REFRIGERANT FROM CHILLER TO PUMP- OUT STORAGE TANK

1. Equalize refrigerant pressure.

 

 

 

 

 

 

 

 

 

a.

Valve positions:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

12

13

14

 

CONDITION

 

 

C

 

C

C

 

C

C

 

 

 

 

 

b.

Slowly open valve 5. When the pressures are

 

equalized, open liquid line valve 7 to allow liquid

 

refrigerant to drain by gravity into the pumpout

 

storage tank.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

12

13

14

 

CONDITION

 

 

C

 

C

 

 

 

C

 

 

 

 

 

2. Transfer the remaining liquid.

 

 

 

 

 

 

 

 

 

a.

Turn off the pumpout condenser water. Place the

 

valves in the following positions:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

12

13

14

 

CONDITION

 

 

 

C

C

 

 

 

C

 

 

 

 

 

b.

Run the pumpout compressor for approximately

 

30 minutes; then close valve 10.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

12

13

14

 

CONDITION

 

 

 

C

C

 

 

 

C

C

 

 

 

 

c.

Turn off the pumpout compressor.

 

 

 

 

 

 

3. Remove any remaining refrigerant.

 

 

 

 

 

 

 

a.

Turn on the chiller water pumps using the PUMP-

 

DOWN LOCKOUT screen, accessed from the

 

CONTROL TEST table. Turn on the pumps manu-

 

ally, if they are not controlled by the PIC II.

b.

Turn on the pumpout condenser water.

c.

Place valves in the following positions:

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

12

13

14

 

CONDITION

 

 

C

 

 

C

 

 

C

C

 

 

 

 

d.

Run the pumpout compressor until the chiller pres-

 

sure reaches 30 psig (207 kPa) for HFC-134a.

 

Then, shut off the pumpout compressor. Warm

 

condenser water will boil off any entrapped liquid

 

refrigerant and the chiller pressure will rise.

e.

When the pressure rises to 40 psig (276 kPa) for

 

HFC-134a, turn on the pumpout compressor until

 

the pressure again reaches 30 psig (207 kPa), and

 

then turn off the pumpout compressor. Repeat this

 

process until the pressure no longer rises. Then,

 

turn on the pumpout compressor and pump until

 

the pressure reaches18 in. Hg. (40 kPa absolute).

f.

Close valves 1a, 1b, 3, 4, 6, 7, and 10.

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

12

13

14

 

CONDITION

C

C

C

C

C

C

C

C

C

C

 

 

 

 

g.Turn off the pumpout condenser water and con- tinue to use the PIC II PUMPDOWN LOCKOUT screen functions, which lock out the chiller com- pressor for operation.

4.Establish a vacuum for service.

To conserve refrigerant, operate the pumpout compressor until the chiller pressure is reduced to 18 in. Hg vac., ref 30 in. bar. (40 kPa abs.) following Step 3e.

Chillers with Isolation Valves

TRANSFER ALL REFRIGERANT TO CHILLER CON- DENSER VESSEL — For chillers with isolation valves, refrigerant can be stored in one chiller vessel or the other with- out the need for an external storage tank.

1. Push refrigerant into the chiller condenser.

 

 

 

 

 

 

a.

Valve positions:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

 

2

3

4

5

 

8

11

12

 

13

 

14

 

 

CONDITION

 

 

 

 

C

C

 

 

C

 

C

 

C

 

C

b.

Using the PIC II controls, turn off the chiller water

 

pumps and pumpout condenser water. If the chiller

 

water pumps are not controlled through the PIC II,

 

turn them off manually.

 

 

 

 

 

 

 

 

 

 

 

c.

Turn on the pumpout compressor to push the liquid

 

refrigerant out of the chiller cooler vessel.

 

 

 

d.

When all liquid refrigerant has been pushed into

 

the chiller condenser vessel, close chiller isolation

 

valve 11.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e. Access the PUMPDOWN LOCKOUT screen on

 

the PIC II CONTROL TEST table to turn on the

 

chiller water pumps. If the chiller water pumps

 

are not controlled by the PIC II, turn them on

 

manually.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

f.

Turn off the pumpout compressor.

 

 

 

 

 

 

 

2. Evacuate the refrigerant gas from chiller cooler vessel.

 

a.

Close pumpout compressor valves 2 and 5, and

 

open valves 3 and 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

 

2

3

4

5

 

8

11

12

 

13

 

14

 

 

CONDITION

 

 

 

C

 

 

C

 

C

C

C

 

C

 

C

b.

Turn on the pumpout condenser water.

 

 

 

 

 

c.

Run the pumpout compressor until the chiller

 

cooler vessel pressure reaches 18 in. Hg vac

 

(40 kPa abs.). Monitor pressures on the CVC/

 

ICVC and on refrigerant gages.

 

 

 

 

 

 

 

d.

Close valve 1a.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e.

Turn off the pumpout compressor.

 

 

 

 

 

 

 

f.

Close valves 1b, 3, and 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

 

2

3

4

5

 

8

11

12

 

13

 

14

 

 

CONDITION

C

C

C

C

C

C

 

C

C

C

 

C

 

C

g.

Turn off the pumpout condenser water.

 

 

 

 

 

h. Proceed to the PUMPDOWN/LOCKOUT function

 

accessed from the CONTROL TEST table to turn

 

off the chiller water pumps and lock out the chiller

 

compressor. Turn off the chiller water pumps man-

 

ually if they are not controlled by the PIC II.

 

 

 

TRANSFER ALL REFRIGERANT TO CHILLER

COOLER VESSEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Push the refrigerant into the chiller cooler vessel.

 

 

 

a.

Valve positions:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

 

2

3

4

5

 

8

11

12

 

13

 

14

 

 

CONDITION

 

 

 

C

 

 

C

 

C

 

C

 

C

 

C

b.

Turn off the chiller water pumps (either through

 

the PIC II controls or manually, if necessary) and

 

the pumpout condenser water.

 

 

 

 

 

 

 

 

 

c.

Turn on the pumpout compressor to push the

 

refrigerant out of the chiller condenser.

 

 

 

 

 

d.

When all liquid refrigerant is out of the chiller con-

 

denser, close the cooler isolation valve 11.

 

 

 

e.

Turn off the pumpout compressor.

 

 

 

 

 

 

 

70

Page 70
Image 70
Carrier 19XR, XRV specifications Chillers with Isolation Valves, Push refrigerant into the chiller condenser