Table 12B — Thermistor Temperature (C) vs. Resistance/Voltage Drop

TEMPERATURE

PIC II

RESISTANCE

(C)

VOLTAGE DROP (V)

(Ohms)

–33

4.722

106 880

–32

4.706

100 260

–31

4.688

94 165

–30

4.670

88 480

–29

4.650

83 170

–28

4.630

78 125

–27

4.608

73 580

–26

4.586

69 250

–25

4.562

65 205

–24

4.538

61 420

–23

4.512

57 875

–22

4.486

54 555

–21

4.458

51 450

–20

4.429

48 536

–19

4.399

45 807

–18

4.368

43 247

–17

4.336

40 845

–16

4.303

38 592

–15

4.269

38 476

–14

4.233

34 489

–13

4.196

32 621

–12

4.158

30 866

–11

4.119

29 216

–10

4.079

27 633

–9

4.037

26 202

–8

3.994

24 827

–7

3.951

23 532

–6

3.906

22 313

–5

3.861

21 163

–4

3.814

20 079

–3

3.765

19 058

–2

3.716

18 094

–1

3.667

17 184

0

3.617

16 325

1

3.565

15 515

2

3.512

14 749

3

3.459

14 026

4

3.406

13 342

5

3.353

12 696

6

3.298

12 085

7

3.242

11 506

8

3.185

10 959

9

3.129

10 441

10

3.074

9 949

11

3.016

9 485

12

2.959

9 044

13

2.901

8 627

14

2.844

8 231

15

2.788

7 855

16

2.730

7 499

17

2.672

7 161

18

2.615

6 840

19

2.559

6 536

20

2.503

6 246

21

2.447

5 971

22

2.391

5 710

23

2.335

5 461

24

2.280

5 225

25

2.227

5 000

26

2.173

4 786

27

2.120

4 583

28

2.067

4 389

29

2.015

4 204

30

1.965

4 028

31

1.914

3 861

32

1.865

3 701

33

1.816

3 549

34

1.768

3 404

35

1.721

3 266

36

1.675

3 134

37

1.629

3 008

TEMPERATURE

PIC II

RESISTANCE

(C)

VOLTAGE DROP (V)

(Ohms)

38

1.585

2 888

39

1.542

2 773

40

1.499

2 663

41

1.457

2 559

42

1.417

2 459

43

1.377

2 363

44

1.338

2 272

45

1.300

2 184

46

1.263

2 101

47

1.227

2 021

48

1.192

1 944

49

1.158

1 871

50

1.124

1 801

51

1.091

1 734

52

1.060

1 670

53

1.029

1 609

54

0.999

1 550

55

0.969

1 493

56

0.941

1 439

57

0.913

1 387

58

0.887

1 337

59

0.861

1 290

60

0.835

1 244

61

0.811

1 200

62

0.787

1 158

63

0.764

1 118

64

0.741

1 079

65

0.719

1 041

66

0.698

1 006

67

0.677

971

68

0.657

938

69

0.638

906

70

0.619

876

71

0.601

836

72

0.583

805

73

0.566

775

74

0.549

747

75

0.533

719

76

0.518

693

77

0.503

669

78

0.488

645

79

0.474

623

80

0.460

602

81

0.447

583

82

0.434

564

83

0.422

547

84

0.410

531

85

0.398

516

86

0.387

502

87

0.376

489

88

0.365

477

89

0.355

466

90

0.344

456

91

0.335

446

92

0.325

436

93

0.316

427

94

0.308

419

95

0.299

410

96

0.291

402

97

0.283

393

98

0.275

385

99

0.267

376

100

0.260

367

101

0.253

357

102

0.246

346

103

0.239

335

104

0.233

324

105

0.227

312

106

0.221

299

107

0.215

285

86

Page 86
Image 86
Carrier 19XR, XRV specifications Thermistor Temperature C vs. Resistance/Voltage Drop, Temperature PIC Resistance

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.