Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors

(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve

TEMPERATURE

RESISTANCE

 

TEMPERATURE

RESISTANCE

TEMPERATURE

RESISTANCE

C

F

ohms

C

 

F

ohms

C

F

ohms

120

248.0

390.0

66

 

150.8

2,011.0

12

53.6

18,090.0

119

246.2

401.2

65

 

149.0

2,083.0

11

51.8

18,972.0

118

244.4

412.8

64

 

147.2

2,157.0

10

50.0

19,903.0

117

242.6

424.8

63

 

145.4

2,235.0

9

48.2

20,883.0

116

240.8

437.2

62

 

143.6

2,315.0

8

46.4

21,918.0

115

239.0

450.0

61

 

141.8

2,400.0

7

44.6

23,013.0

114

237.2

462.5

60

 

140.0

2,488.0

6

42.8

24,117.0

113

235.4

475.5

59

 

138.2

2,579.0

5

41.0

25,396.0

112

233.6

488.9

58

 

136.4

2,675.0

4

39.2

26,686.0

111

231.8

502.7

57

 

134.6

2,774.0

3

37.4

28,052.0

110

230.0

517.0

56

 

132.8

2,878.0

2

35.6

29,498.0

109

228.2

531.0

55

 

131.0

2,986.0

1

33.8

31,030.0

108

226.4

545.6

54

 

129.2

3,099.0

0

32.0

32,654.0

107

224.6

560.5

53

 

127.4

3,217.0

–1

30.2

34,367.0

106

222.8

576.0

52

 

125.6

3,340.0

–2

28.4

36,182.0

105

221.0

592.0

51

 

123.8

3,469.0

–3

26.6

38,109.0

104

219.2

608.5

50

 

122.0

3,603.0

–4

24.8

40,153.0

103

217.4

625.5

49

 

120.2

3,743.0

–5

23.0

42,324.0

102

215.6

643.0

48

 

118.4

3,889.0

–6

21.2

44,617.0

101

213.8

661.2

47

 

116.6

4,042.0

–7

19.4

47,052.0

100

212.0

680.0

46

 

114.8

4,203.0

–8

17.6

49,640.0

99

210.2

700.0

45

 

113.0

4,370.0

–9

15.8

52,392.0

98

208.4

720.6

44

 

111.2

4,544.0

–10

14.0

55,319.0

97

206.6

742.0

43

 

109.4

4,727.0

–11

12.2

58,415.0

96

204.8

764.1

42

 

107.6

4,918.0

–12

10.4

61,711.0

95

203.0

787.0

41

 

105.8

5,117.0

–13

8.6

65,219.0

94

201.2

810.8

40

 

104.0

5,327.0

–14

6.8

68,957.0

93

199.4

835.5

39

 

102.2

5,546.0

–15

5.0

72,940.0

92

197.6

861.0

38

 

100.4

5,774.0

–16

3.2

77,162.0

91

195.8

888.5

37

 

98.6

6,014.0

–17

1.4

81,662.0

90

194.0

915.0

36

 

96.8

6,266.0

–18

–0.4

86,463.0

89

192.2

944.0

35

 

95.0

6,530.0

–19

–2.2

91,588.0

88

190.4

974.0

34

 

93.2

6,806.0

–20

–4.0

97,060.0

87

188.6

1005.0

33

 

91.4

7,096.0

–21

–5.8

102,868.0

86

186.8

1037.0

32

 

89.6

7,401.0

–22

–7.6

109,075.0

85

185.0

1070.0

31

 

87.8

7,720.0

–23

–9.4

115,710.0

84

183.2

1104.0

30

 

86.0

8,056.0

–24

–11.2

122,807.0

83

181.4

1140.0

29

 

84.2

8,407.0

–25

–13.0

130,402.0

82

179.6

1177.0

28

 

82.4

8,776.0

–26

–14.8

138,482.0

81

177.8

1215.0

27

 

80.6

9,164.0

–27

–16.6

147,134.0

80

176.0

1255.0

26

 

78.8

9,571.0

–28

–18.4

156,404.0

79

174.2

1297.0

25

 

77.0

10,000.0

–29

–20.2

166,342.0

78

172.4

1340.0

24

 

75.2

10,449.0

–30

–22.0

177,000.0

77

170.6

1385.0

23

 

73.4

10,921.0

–31

–23.8

188,340.0

76

168.8

1431.0

22

 

71.6

11,418.0

–32

–25.6

200,510.0

75

167.0

1480.0

21

 

69.8

11,942.0

–33

–27.4

213,570.0

74

165.2

1530.0

20

 

68.0

12,493.0

–34

–29.2

227,610.0

73

163.4

1582.0

19

 

66.2

13,071.0

–35

–31.0

242,700.0

72

161.6

1637.0

18

 

64.4

13,681.0

–36

–32.8

258,730.0

71

159.8

1693.0

17

 

62.6

14,323.0

–37

–34.6

275,970.0

70

158.0

1752.0

16

 

60.8

15,000.0

–38

–36.4

294,520.0

69

156.2

1813.0

15

 

59.0

15,714.0

–39

–38.2

314,490.0

68

154.4

1876.0

14

 

57.2

16,464.0

–40

–40.0

336,000.0

67

152.6

1943.0

13

 

55.4

17,255.0

 

 

 

Table 6 — Outdoor Air, Return Air, and Supply Air

Temperature Sensors (CRTEMPSN001A00 or HH79NZ039) — Thermistor Resolution

 

RANGE

RESOLUTION

Low

 

High

 

 

F

 

F

F

–41

 

–18

4.0

–17

 

14

2.0

15

 

28

1.0

29

 

47

0.8

48

 

86

0.7

87

 

108

0.8

109

 

126

1.0

127

 

171

2.0