Table 11 — Fan Performance 580F036 — Vertical Discharge Units, Alternate Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

643

0.15

152

768

0.22

222

870

0.30

296

958

0.37

373

1037

0.46

454

1000

683

0.19

191

804

0.27

268

904

0.35

348

991

0.43

430

1069

0.52

517

1100

725

0.24

237

842

0.32

321

939

0.41

407

1025

0.50

496

1102

0.59

588

1200

767

0.29

291

880

0.38

382

976

0.48

474

1060

0.57

570

1136

0.67

668

1300

811

0.35

352

920

0.45

451

1013

0.55

550

1095

0.66

652

1170

0.76

756

1400

855

0.43

423

960

0.53

529

1051

0.64

636

1132

0.75

744

1205

0.86

855

1500

900

0.51

504

1002

0.62

617

1090

0.74

731

1169

0.85

846

1242

0.97

963

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

1110

0.54

538

1177

0.63

627

1239

0.72

718

1298

0.82

813

1355

0.92

911

1000

1141

0.61

607

1207

0.70

700

1269

0.80

796

1328

0.90

895

1384

1.00

998

1100

1173

0.69

683

1238

0.79

781

1300

0.89

883

1358

0.99

987

1414

1.10

1094

1200

1205

0.77

768

1270

0.88

872

1332

0.98

979

1389

1.09

1088

1300

1239

0.87

863

1303

0.98

972

1364

1.09

1084

1400

1273

0.97

967

1337

1.09

1082

1500

1309

1.09

1082

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 685 to 1045 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 1.20.

3.See page 36 for general fan performance notes.

Table 12 — Fan Performance 580F036 — Vertical Discharge Units, High-Static Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

643

0.15

152

768

0.22

222

870

0.30

296

958

0.37

373

1037

0.46

454

1000

683

0.19

191

804

0.27

268

904

0.35

348

991

0.43

430

1069

0.52

517

1100

725

0.24

237

842

0.32

321

939

0.41

407

1025

0.50

496

1102

0.59

588

1200

767

0.29

291

880

0.38

382

976

0.48

474

1060

0.57

570

1136

0.67

668

1300

811

0.35

352

920

0.45

451

1013

0.55

550

1095

0.66

652

1170

0.76

756

1400

855

0.43

423

960

0.53

529

1051

0.64

636

1132

0.75

744

1205

0.86

855

1500

900

0.51

504

1002

0.62

617

1090

0.74

731

1169

0.85

846

1242

0.97

963

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

1110

0.54

538

1177

0.63

627

1239

0.72

718

1298

0.82

813

1355

0.92

911

1000

1141

0.61

607

1207

0.70

700

1269

0.80

796

1328

0.90

895

1384

1.00

998

1100

1173

0.69

683

1238

0.79

781

1300

0.89

883

1358

0.99

987

1414

1.10

1094

1200

1205

0.77

768

1270

0.88

872

1332

0.98

979

1389

1.09

1088

1444

1.21

1200

1300

1239

0.87

863

1303

0.98

972

1364

1.09

1084

1421

1.21

1199

1475

1.32

1316

1400

1273

0.97

967

1337

1.09

1082

1397

1.21

1200

1453

1.33

1320

1507

1.45

1443

1500

1309

1.09

1082

1371

1.21

1204

1430

1.33

1327

1486

1.46

1453

1540

1.59

1581

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 2.40.

3.Seee page 36 for general fan performance notes.

 

 

 

 

Table 13 — Fan Performance 580F048 — Vertical Discharge Units, Standard Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD MOTOR (DIRECT DRIVE)

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

Low Speed

 

 

 

 

 

 

High Speed

 

 

 

 

 

 

 

 

208 V

 

 

230, 460, 575 V

 

 

208 V

 

 

230, 460, 575 V

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP

 

Bhp

 

Watts

ESP

 

Bhp

 

Watts

ESP

Bhp

Watts

ESP

 

Bhp

 

Watts

 

1200

 

0.68

 

0.41

 

458

0.74

 

0.45

 

506

0.74

0.51

572

0.85

 

0.56

 

632

 

1300

 

0.61

 

0.42

 

471

0.67

 

0.46

 

521

0.66

0.52

589

0.78

 

0.58

 

651

 

1400

 

0.53

 

0.45

 

503

0.59

 

0.49

 

556

0.59

0.54

616

0.70

 

0.60

 

681

 

1500

 

0.45

 

0.47

 

536

0.51

 

0.52

 

593

0.52

0.56

631

0.63

 

0.62

 

698

 

1600

 

0.36

 

0.49

 

557

0.42

 

0.54

 

616

0.45

0.58

654

0.56

 

0.64

 

723

 

1700

 

0.26

 

0.52

 

584

0.32

 

0.57

 

646

0.37

0.60

678

0.48

 

0.66

 

750

 

1800

 

0.15

 

0.54

 

610

0.22

 

0.60

 

674

0.30

0.62

698

0.41

 

0.68

 

772

 

1900

 

0.04

 

0.56

 

629

0.11

 

0.62

 

696

0.23

0.64

720

0.34

 

0.70

 

796

 

2000

 

 

 

 

 

0.16

0.66

744

0.26

 

0.73

 

823

 

 

LEGEND

 

 

 

 

 

 

 

 

See page 36 for general fan performance notes.

 

 

 

 

Bhp

Brake Horsepower Input to Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

26