Table 1 — Physical Data (cont)

UNIT SIZE 580F

 

 

 

036

048

 

060

072 AND 073

FURNACE SECTION

 

 

 

 

 

 

 

 

 

Rollout Switch Cutout

 

 

 

 

 

 

 

 

 

Temp (F)††

 

 

 

195

195

 

195

195

Burner Orifice Diameter

 

 

 

 

 

 

 

 

(in. ...drill size)

 

 

 

 

 

 

 

 

 

Natural Gas

 

Std

074

.113...33

.113...33

 

.113...33

.113...33

 

 

 

114/115

.113...33

.113...33

 

.113...33

.113...33

 

 

 

149/150

.129...30

 

.129...30

.129...30

 

 

 

060N

.102...38

.102...38

 

.102...38

 

 

 

090N

.102...38

.102...38

 

.102...38

 

 

 

120N

.116...32

 

.116...32

Liquid Propane

 

Alt

074

.089...43

.089...43

 

.089...43

.089...43

 

 

 

114/115

.089...43

.089...43

 

.089...43

.089...43

 

 

 

149/150

.104...37

 

.104...37

.104...37

 

 

 

060N

.082...45

.082...45

 

.082...45

 

 

 

090N

.082...45

.082...45

 

.082...45

Thermostat Heat Anticipator

 

120N

.094...42

 

.094...42

 

 

 

 

 

 

 

 

Setting (amps)

 

 

 

 

 

 

 

 

 

208/230 v and 575

Stage 1

 

 

.14

.14

 

.14

.14

 

Stage 2

 

 

.14

.14

 

.14

.14

460 v

Stage 1

 

 

.14

.14

 

.14

.14

 

Stage 2

 

114

.14

.14

 

.14

.14

Gas Input (Btuh)

CA High Output 3-Phase Units

 

115,000

 

 

 

 

149

150,000

 

150,000

 

Standard Units

 

074

74,000/—

74,000/—

 

74,000/—

74,000/—

 

(Stage 2/ Stage 1)

 

115***

115,000/82,000

115,000/—

 

115,000/—

115,000/—

 

 

 

150***

150,000/120,000

 

150,000/120,000

150,000/120,000

 

Low NOx Units

 

060N†††

60,000

60,000

 

60,000

 

 

 

090N†††

90,000

90,000

 

90,000

 

 

 

120N†††

120,000

 

120,000

Efficiency (Steady

 

 

 

 

 

 

 

 

 

State) (%)

 

 

 

80

80

 

80

80

Temperature Rise Range

 

074

25-55

25-55

 

25-55

25-55

 

 

 

114/115

55-85

35-65

 

35-65

35-65

 

 

 

149/150

50-80

 

50-80

50-80

 

 

 

060N

20-50

20-50

 

20-50

 

 

 

090N

30-60

30-60

 

30-60

Manifold Pressure (in. wg)

 

120N

40-70

 

40-70

 

 

 

 

 

 

 

 

Natural Gas

 

Std

 

3.5

3.5

 

3.5

3.5

Liquid Propane

 

Alt

 

3.5

3.5

 

3.5

3.5

Gas Valve Quantity

 

 

 

1

1

 

1

1

Gas Valve Pressure Range

 

 

 

 

 

 

 

 

Psig

 

 

 

0.180-0.487

0.180-0.487

 

0.180-0.487

0.180-0.487

in. wg

 

 

 

5.0-13.5

5.0-13.5

 

5.0-13.5

5.0-13.5

Field Gas Connection

 

 

 

1/

1/

 

1/

 

1/

Size (in.)

 

 

 

 

2

 

 

 

 

2

2

 

 

2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

Standard Compressor

 

 

 

 

450 ± 50

 

 

 

500 ± 50

Internal Relief (Differential)

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

428

 

 

 

428

Reset (Auto.)

 

 

 

 

320

 

 

 

320

LOSS-OF-CHARGE (LOW-PRESSURE SWITCH) (psig)

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

 

7 ± 3

 

 

Reset (Auto.)

 

 

 

 

22 ± 7

 

 

FREEZE PROTECTION

 

 

 

 

 

 

 

 

 

THERMOSTAT (F)

 

 

 

 

 

 

 

 

 

Opens

 

 

 

 

30 ± 5

 

 

Closes

 

 

 

 

45 ± 5

 

 

OUTDOOR-AIR INLET SCREENS

 

 

Cleanable. Screen size and quantity varies with option selected.

RETURN-AIR FILTERS

 

 

 

 

Throwaway

 

 

Quantity...Size (in.)

 

 

 

 

2...16 x 25 x 2

 

 

 

 

LEGEND

Al

Aluminum

Bhp —

Brake Horsepower

Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your local rep- resentative for details about coated fins.

†Weight of 14-in. roof curb. **Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or reset- ting thermostat.

California rated three-phase high heat models.

***Three phase standard high-heat models have heating input values as shown. Single phase standard high heat models have one-stage heating with heating input values as follows:

580FJV036115 — 115,000 Btuh

580FJV048150 — 150,000 Btuh

580FJV060150 — 150,000 Btuh

†††California SCAQMD compliant Low NOx models have combustion products that are controlled to 40 nanograms per joule or less.

9

Page 9
Image 9
Bryant 580F installation instructions Physical Data cont