Table 8 — Fan Rpm at Motor Pulley Settings*

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

580F

 

0

1/

1

11/

2

 

21/

3

31/

 

4

41/

5

51/

6

 

 

 

2

 

2

 

 

2

 

2

 

 

2

 

2

 

036†

1045

1009

973

937

901

 

865

829

793

 

757

721

685

036**

 

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

048†

1175

1135

1094

1054

1013

 

973

932

892

 

851

811

770

048**

 

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

060†

1192

1166

1140

1114

1087

 

1061

1035

1009

 

983

957

930

904

878

060**

 

1685

1647

1608

1570

1531

 

1493

1454

1416

 

1377

1339

1300

072, 073††

1460

1421

1382

1343

1304

 

1265

1226

1187

 

1148

1109

1070

072, 073**

 

1685

1647

1608

1570

1531

 

1493

1454

1416

 

1377

1339

1300

*Approximate fan rpm shown.

†Indicates alternate motor and drive package.

**Indicates high-static motor and drive package. ††Indicates standard motor and drive package.

Table 9 — Motor Data

UNIT

EVAPORATOR-FAN

UNIT

MAXIMUM ACCEPTABLE

MAXIMUM ACCEPTABLE

MAXIMUM

580F

MOTOR

VOLTAGE

CONTINUOUS BHP*

OPERATING WATTS

AMP DRAW

 

 

208/230

 

 

2.8

 

Standard

460

0.34

440

1.3

 

 

575

 

 

1.3

 

 

208/230

 

 

4.9

036

Alternate

460

1.20

1000

2.1

 

 

575

 

 

2.1

 

 

208/230

 

 

6.0

 

High Static

460

2.40

2120

3.0

 

 

575

 

 

3.0

 

 

208/230

 

 

3.5

 

Standard

460

0.75

850

1.8

 

 

575

 

 

1.8

 

 

208/230

 

 

4.9

048

Alternate

460

1.20

1000

2.1

 

 

575

 

 

2.1

 

 

208/230

 

 

6.0

 

High Static

460

2.40

2120

3.0

 

 

575

 

 

3.0

 

 

208/230

 

 

5.9

 

Standard

460

1.20

1340

3.2

 

 

575

 

 

3.2

 

 

208/230

 

 

10.1/6.7†

060

Alternate

460

1.30/2.40†

2120

3.0

 

 

575

 

 

3.0

 

 

208/230

 

 

8.6

 

High Static

460

2.90

2562

3.9

 

 

575

 

 

3.9

 

 

208/230

 

 

6.7

 

Standard

460

2.40

2120

3.0

072, 073

 

575

 

 

3.0

 

208/230

 

 

8.6

 

 

 

 

 

High Static

460

2.90

2562

3.9

 

 

575

 

 

3.9

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horse- power range of the motors can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in nui- sance tripping or premature motor failure. Unit warranty will not be affected.

†Single phase/three-phase.

NOTES:

1.All indoor-fan motors 5 hp and larger meet the minimum efficiency require- ments as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.

2.High-static motor not available on single-phase units.

 

 

Table 10 — Fan Performance 580F036 — Vertical Discharge Units, Standard Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD MOTOR (DIRECT DRIVE)

 

 

 

 

 

 

 

Airflow

 

 

 

Low Speed

 

 

 

 

 

 

High Speed

 

 

 

 

 

 

208 V

 

 

230, 460, 575 V

 

 

208 V

 

 

230, 460, 575 V

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

ESP

 

Bhp

Watts

ESP

 

Bhp

 

Watts

ESP

Bhp

Watts

ESP

 

Bhp

 

Watts

900

0.49

 

0.21

253

0.50

 

0.23

 

277

0.51

0.26

307

0.55

 

0.31

 

363

1000

0.42

 

0.23

270

0.43

 

0.25

 

292

0.43

0.27

321

0.51

 

0.32

 

374

1100

0.37

 

0.24

287

0.38

 

0.26

 

307

0.39

0.28

335

0.46

 

0.33

 

385

1200

0.33

 

0.26

304

0.33

 

0.27

 

323

0.34

0.29

349

0.40

 

0.34

 

397

1300

0.27

 

0.27

321

0.28

 

0.29

 

338

0.28

0.31

364

0.34

 

0.34

 

408

1400

0.20

 

0.29

338

0.23

 

0.30

 

354

0.25

0.32

378

 

 

1500

0.16

 

0.30

355

0.18

 

0.31

 

369

0.20

0.33

392

 

 

 

LEGEND

See page 36 for general fan performance notes.

Bhp —

Brake Horsepower Input to Fan

 

ESP —

External Static Pressure (in. wg)

 

25

Page 25
Image 25
Bryant 580F installation instructions Fan Rpm at Motor Pulley Settings, Motor Data