R. CO2 Sensor Configuration

minimum position (configuration item number 15), unless the remote potentiometer is used to override it.

For the demand ventilation control logic, the user configures the lower and upper actuator position to establish the base ventilation rate (IAQMIN_SP) and the design ventilation rate (ECONOMIN_SP) for full occupancy. When the EconoMi$er+ damper is being modulated for demand venti- lation control, the damper position will be between IAQMIN_SP and ECONOMIN_SP. The upper IAQ differen- tial set point is DAQHI. The lower IAQ differential set point is DAQLO.

The differential set points represent the differential CO2 level (in ppm) above the outdoor reference IAQ levels. Normally, the outdoor reference IAQ levels are around 400 ppm, but the value should be configured based on the reference levels taken at the job site.

The following equation is used to determine EconoMi$er+ damper position (ECONOMIN_POS):

(ECONOMIN_SP – IAQMIN_SP) * (IAQ – OAQ – DAQLO)

IAQMIN_SP + =

(DAQHI – DAQLO)

R. CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 7.

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode 2 times. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. See Table 7.

4.Press Enter to lock in the selection.

Press Mode to exit and resume normal operation. The cus- tom settings of the CO2 sensor can be changed any time after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode 2 times. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

S.Dehumidification of Fresh Air with Demand Control Ven- tilation (DCV)

Information from ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) indicates that the largest humidity load on any zone is the fresh air intro- duced. For some applications, a device such as a energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling pro- cesses are more than adequate to remove the humidity loads for most commercial applications.

This makes the control of the dehumidification device simple when using the enthalpy or differential enthalpy sensor. The enthalpy sensor or differential enthalpy sensor is installed on the equipment to determine economizer operation. The high enthalpy signal from the temperature and humidity sensors or differential temperature and humidity sensors can be used to turn on the outdoor air moisture removal device any time fresh air is required for the space.

The energy recovery device should be sized for maximum latent and sensible conditioning at maximum ventilation on a design day.

A calculation for leaving-air temperature on a low ambient, low ventilation day should also be done to determine the supply-air temperature of the return and pre-conditioned outside air. The design should produce air temperature somewhat near room conditions to prevent reheat of the air mixture. The energy recovery device should be interlocked with the heat to turn off the device when in the heat mode.

DAMPER

 

 

 

POSTION

 

 

 

 

 

FULL OCCUPANCY

 

ECONOMIZER

 

VENTILATION RATE

 

MINIMUM

 

 

 

OCCUPIED

 

 

 

DAMPER

 

 

 

POSITION

 

 

 

(ECONOMIN_SP)

 

 

 

 

VENTILATION FOR PEOPLE

IAQ

 

 

 

MINIMUM

 

 

 

ECONOMIZER

 

 

 

POSITION

 

 

 

SET POINT

VENTILATION FOR SOURCES

(IAQMIN_SP)

 

 

 

 

 

 

CO2 LEVEL

OUTDOOR REFERENCE

100

700

INSIDE/OUTSIDE CO2 DIFFERENTIAL

LEVEL (OAQ)= 400

500

1100

INSIDE CO2 CONCENTRATION

AQ

AQ

DIFFERENTIAL

DIFFERENTIAL

LOW (DAQLO)

HIGH (DAQHI)

Fig. 32 — Demand Ventilation Control

Table 7 — CO2 Sensor* Standard Settings

 

 

 

VENTILATION

ANALOG

CO2 CONTROL

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

RELAY SETPOINT

HYSTERESIS

 

 

 

(cfm/Person)

OUTPUT

RANGE (ppm)

(ppm)

(ppm)

 

 

 

 

 

1

Interface with Standard

Proportional

Any

4-20 mA

0-2000

1000

50

2

Proportional

Any

7-20 mA

0-2000

1000

50

Building Control System

3

Exponential

Any

4-20 mA

0-2000

1100

50

 

4

 

Proportional

15

4-20 mA

0-1100

1100

50

5

Economizer

Proportional

20

4-20 mA

0- 900

900

50

6

Exponential

15

4-20 mA

0-1100

1100

50

 

7

 

Exponential

20

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/ Loading Docks

Proportional

4-20 mA

0-2000

700

50

LEGEND

ppm — Parts Per Million

*Available sensor part numbers are listed in Table 4.

23

Page 23
Image 23
Bryant 580F R. CO2 Sensor Configuration, Demand Ventilation Control, CO2 Sensor* Standard Settings