Table 29 — Fan Performance 580F060 —
Alternate Motor (Belt Drive)*
AIRFLOW |
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
| ||||
| 0.2 |
|
| 0.4 |
|
| 0.6 |
|
| 0.8 |
|
| 1.0 |
| |
(Cfm) |
|
|
|
|
|
|
|
|
|
| |||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts |
1500 | 790 | 0.40 | 353 | 896 | 0.53 | 470 | 990 | 0.67 | 599 | 1074 | 0.83 | 738 | 1151 | 1.00 | 886 |
1600 | 828 | 0.46 | 413 | 930 | 0.60 | 535 | 1021 | 0.75 | 669 | 1103 | 0.91 | 812 | 1179 | 1.09 | 965 |
1700 | 866 | 0.54 | 479 | 964 | 0.68 | 607 | 1053 | 0.84 | 746 | 1133 | 1.01 | 894 | 1207 | 1.18 | 1051 |
1800 | 905 | 0.62 | 553 | 1000 | 0.77 | 687 | 1085 | 0.94 | 831 | 1164 | 1.11 | 984 | 1236 | 1.29 | 1146 |
1900 | 944 | 0.71 | 635 | 1036 | 0.87 | 775 | 1119 | 1.04 | 924 | 1195 | 1.22 | 1082 | — | — | — |
2000 | 984 | 0.82 | 725 | 1072 | 0.98 | 871 | 1153 | 1.15 | 1025 | — | — | — | — | — | — |
2100 | 1024 | 0.93 | 824 | 1109 | 1.10 | 976 | 1188 | 1.28 | 1136 | — | — | — | — | — | — |
2200 | 1064 | 1.05 | 932 | 1147 | 1.23 | 1090 | — | — | — | — | — | — | — | — | — |
2300 | 1105 | 1.18 | 1050 | — | — | — | — | — | — | — | — | — | — | — | — |
2400 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
2500 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
|
|
|
|
|
|
|
|
|
|
|
| ||||
AIRFLOW |
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
| ||||
| 1.2 |
|
| 1.4 |
|
| 1.6 |
|
| 1.8 |
|
| 2.0 |
| |
(Cfm) |
|
|
|
|
|
|
|
|
|
| |||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts |
1500 | 1223 | 1.18 | 1045 | — | — | — | — | — | — | — | — | — | — | — | — |
1600 | 1249 | 1.27 | 1127 | — | — | — | — | — | — | — | — | — | — | — | — |
1700 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
1800 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
1900 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
2000 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
2100 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
2200 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
2300 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
2400 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
2500 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
LEGEND
Bhp — Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 875 to 1192 rpm. All other rpms require a field- supplied drive.
NOTES:
1.Boldface indicates
2.Maximum continuous bhp is 1.30.
3.See page 36 for general fan performance notes.
Table 30 — Fan Performance 580F060 —
Alternate Motor (Belt Drive)*
AIRFLOW |
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
| ||||
| 0.2 |
|
| 0.4 |
|
| 0.6 |
|
| 0.8 |
|
| 1.0 |
| |
(Cfm) |
|
|
|
|
|
|
|
|
|
| |||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts |
1500 | 790 | 0.40 | 353 | 896 | 0.53 | 470 | 990 | 0.67 | 599 | 1074 | 0.83 | 738 | 1151 | 1.00 | 886 |
1600 | 828 | 0.46 | 413 | 930 | 0.60 | 535 | 1021 | 0.75 | 669 | 1103 | 0.91 | 812 | 1179 | 1.09 | 965 |
1700 | 866 | 0.54 | 479 | 964 | 0.68 | 607 | 1053 | 0.84 | 746 | 1133 | 1.01 | 894 | 1207 | 1.18 | 1051 |
1800 | 905 | 0.62 | 553 | 1000 | 0.77 | 687 | 1085 | 0.94 | 831 | 1164 | 1.11 | 984 | 1236 | 1.29 | 1146 |
1900 | 944 | 0.71 | 635 | 1036 | 0.87 | 775 | 1119 | 1.04 | 924 | 1195 | 1.22 | 1082 | 1266 | 1.41 | 1248 |
2000 | 984 | 0.82 | 725 | 1072 | 0.98 | 871 | 1153 | 1.15 | 1025 | 1227 | 1.34 | 1189 | 1297 | 1.53 | 1360 |
2100 | 1024 | 0.93 | 824 | 1109 | 1.10 | 976 | 1188 | 1.28 | 1136 | 1260 | 1.47 | 1305 | 1328 | 1.67 | 1481 |
2200 | 1064 | 1.05 | 932 | 1147 | 1.23 | 1090 | 1223 | 1.41 | 1256 | 1294 | 1.61 | 1430 | 1360 | 1.81 | 1612 |
2300 | 1105 | 1.18 | 1050 | 1185 | 1.37 | 1215 | 1259 | 1.56 | 1386 | 1328 | 1.76 | 1566 | 1393 | 1.97 | 1752 |
2400 | 1146 | 1.33 | 1179 | 1223 | 1.52 | 1349 | 1295 | 1.72 | 1527 | 1362 | 1.93 | 1711 | 1426 | 2.14 | 1903 |
2500 | 1187 | 1.48 | 1317 | 1262 | 1.68 | 1494 | 1332 | 1.89 | 1677 | 1398 | 2.10 | 1868 | 1460 | 2.33 | 2065 |
|
|
|
|
|
|
|
|
|
|
|
| ||||
AIRFLOW |
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
| ||||
| 1.2 |
|
| 1.4 |
|
| 1.6 |
|
| 1.8 |
|
| 2.0 |
| |
(Cfm) |
|
|
|
|
|
|
|
|
|
| |||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts |
1500 | 1223 | 1.18 | 1045 | 1291 | 1.36 | 1212 | 1355 | 1.56 | 1388 | 1415 | 1.77 | 1573 | 1473 | 1.99 | 1765 |
1600 | 1249 | 1.27 | 1127 | 1316 | 1.46 | 1298 | 1379 | 1.66 | 1478 | 1439 | 1.87 | 1665 | 1496 | 2.09 | 1860 |
1700 | 1277 | 1.37 | 1217 | 1342 | 1.57 | 1392 | 1404 | 1.77 | 1575 | 1463 | 1.99 | 1766 | 1520 | 2.21 | 1965 |
1800 | 1305 | 1.48 | 1316 | 1369 | 1.68 | 1495 | 1430 | 1.89 | 1681 | 1489 | 2.11 | 1876 | 1545 | 2.34 | 2078 |
1900 | 1333 | 1.60 | 1423 | 1397 | 1.81 | 1606 | 1457 | 2.02 | 1797 | 1514 | 2.25 | 1995 | — | — | — |
2000 | 1363 | 1.73 | 1540 | 1425 | 1.94 | 1727 | 1484 | 2.16 | 1922 | 1541 | 2.39 | 2124 | — | — | — |
2100 | 1393 | 1.87 | 1665 | 1454 | 2.09 | 1857 | 1512 | 2.31 | 2056 | — | — | — | — | — | — |
2200 | 1424 | 2.03 | 1801 | 1484 | 2.25 | 1997 | — | — | — | — | — | — | — | — | — |
2300 | 1455 | 2.19 | 1946 | — | — | — | — | — | — | — | — | — | — | — | — |
2400 | 1487 | 2.37 | 2103 | — | — | — | — | — | — | — | — | — | — | — | — |
2500 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
LEGEND
Bhp — Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field- supplied drive.
NOTES:
1.Boldface indicates
2.Maximum continuous bhp is 2.40.
3.See page 36 for general fan performance notes.