Table 2A — Electrical Data (Without Convenience Outlet)

UNIT

NOMINAL

IFM

VOLTAGE

COMPR

 

OFM

IFM

COMBUSTION

POWER SUPPLY

DISCONNECT

RANGE

 

(ea)

 

(ea)

 

FAN MOTOR

 

 

 

SIZE*

 

580F

VOLTAGE

TYPE

Min

Max

RLA

 

LRA

Hp

 

FLA

FLA

FLA

MCA

MOCP†

FLA

 

LRA

 

 

 

 

 

 

 

208/230-1-60

Std

187

254

16.2

 

96.0

1/4

 

1.4

3.5

.6

25.2/25.2

30/30

24/24

 

106/106

 

Alt

 

 

4.9

26.6/26.6

35/35

26/26

 

111/111

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

17.7/17.7

25/25

17/17

 

85/

85

 

208/230-3-60

Alt

187

254

10.2

 

75.0

1/4

 

1.4

4.9

.6

19.1/19.1

25/25

19/19

 

90/

90

036

 

High

 

 

 

 

 

 

 

 

5.2

 

19.4/19.4

25/25

19/19

 

109/109

 

Std

 

 

 

 

 

 

 

 

1.3

 

7.6

15

7

 

44

(3 Tons)

 

 

 

 

 

 

 

 

 

 

 

460-3-60

Alt

414

508

4.4

 

40.0

1/4

 

0.8

2.1

.3

8.4

15

8

 

48

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

2.6

 

8.9

15

9

 

57

 

 

Std

 

 

 

 

 

 

 

 

1.3

 

5.5

15

6

 

35

 

575-3-60

Alt

518

632

3.7

 

31.0

1/4

 

0.8

2.1

.3

6.0

15

7

 

37

 

 

High

 

 

 

 

 

 

 

 

2.6

 

6.3

15

7

 

56

 

 

208/230-1-60

Std

187

254

23.3

 

118.0

1/4

 

1.4

3.5

.6

34.0/34.0

40/40

32/32

 

129/129

 

Alt

 

 

4.9

35.4/35.4

45/45

34/34

 

133/133

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

24.2/24.2

30/30

23/23

 

101/101

 

208/230-3-60

Alt

187

254

15.4

 

90.0

1/4

 

1.4

4.9

.6

25.6/25.6

30/30

25/25

 

105/105

048

 

High

 

 

 

 

 

 

 

 

5.2

 

25.9/25.9

30/30

25/25

 

124/124

 

Std

 

 

 

 

 

 

 

 

1.8

 

13.0

20

13

 

51

(4 Tons)

 

 

 

 

 

 

 

 

 

 

 

460-3-60

Alt

414

508

8.3

 

45.0

1/4

 

0.8

2.1

.3

13.3

20

13

 

53

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

2.6

 

13.8

20

13

 

62

 

 

Std

 

 

 

 

 

 

 

 

1.8

 

9.2

15

10

 

41

 

575-3-60

Alt

518

632

6.4

 

36.0

1/4

 

0.8

2.1

.3

9.3

15

10

 

42

 

 

High

 

 

 

 

 

 

 

 

2.6

 

9.7

15

10

 

49

 

208/230-1-60

Std

187

254

28.8

 

147.0

1/4

 

1.4

5.9

.6

43.3/43.3

60/60

42/42

 

161/161

 

Alt

 

 

6.6

44.0/44.0

60/60

42/42

 

184/184

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

5.9

 

27.3/27.3

35/35

27/27

 

128/128

 

208/230-3-60

Alt

187

254

16.0

 

114.0

1/4

 

1.4

5.2

.6

26.6/26.6

35/35

26/26

 

148/148

060

 

High

 

 

 

 

 

 

 

 

7.5

 

28.9/28.9

35/35

29/29

 

174/174

 

Std

 

 

 

 

 

 

 

 

3.1

 

13.2

20

13

 

71

(5 Tons)

 

 

 

 

 

 

 

 

 

 

 

460-3-60

Alt

414

508

7.4

 

64.0

1/4

 

0.8

2.6

.3

13.5

20

13

 

81

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

3.4

 

13.5

20

13

 

93

 

 

Std

 

 

 

 

 

 

 

 

3.1

 

9.7

15

11

 

58

 

575-3-60

Alt

518

632

6.2

 

52.0

1/4

 

0.8

2.6

.3

9.9

15

11

 

65

 

 

 

High

 

 

 

 

 

 

 

 

3.4

 

9.9

15

11

 

76

 

208/230-3-60

Std

187

254

20.6

 

146.0

1/4

 

1.4

5.2

.6

32.4/32.4

40/40

31/31

 

180/180

 

High

 

 

7.5

34.7/34.7

40/40

34/34

 

205/205

 

 

 

 

 

 

 

 

 

 

 

 

072

460-3-60

Std

414

508

9.5

 

73.0

1/4

 

0.9

2.6

.3

15.4

20

15

 

90

(6 Tons)

High

 

 

3.4

16.2

20

16

 

103

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

Std

518

632

7.6

 

58.4

1/4

 

0.6

2.6

.3

11.4

15

12

 

75

 

High

 

 

3.4

11.9

15

13

 

86

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

Std

187

254

20.6

 

146.0

1/4

 

1.4

5.2

.6

32.4/32.4

40/40

31/31

 

180/180

 

High

 

 

7.5

34.7/34.7

40/40

34/34

 

205/205

 

 

 

 

 

 

 

 

 

 

 

 

073

460-3-60

Std

414

508

9.5

 

73.0

1/4

 

0.9

2.6

.3

15.4

20

15

 

90

(6 Tons)

High

 

 

3.4

16.2

20

16

 

103

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

Std

518

632

7.6

 

58.4

1/4

 

0.6

2.6

.3

11.4

15

12

 

79

 

High

 

 

3.4

11.9

15

13

 

86

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA — Full Load Amps

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

% Voltage Imbalance = 100 x

7

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

%Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

=457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

457

=1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

3.For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:

MCA New = MCA unit only + MCA of Power Exhaust

For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust.

MCA New = 28.9 amps + 1.6 amps = 30.5 amps

If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

POWER EXHAUST

MCA

MCA

MCA

MOCP

(for separate

PART NO.

(230 v)

(460 v)

(575 v)

power source)

 

 

 

 

CRPWREXH030A00

1.6

N/A

0.64

15

CRPWREXH021A00

N/A

0.9

N/A

15

CRPWREXH022A00

3.3

N/A

1.32

15

CRPWREXH023A00

N/A

1.8

N/A

15

CRPWREXH028A00

1.7

N/A

0.68

15

CRPWREXH029A00

N/A

1.0

N/A

15