58

MODE OF OPERATION

 

PUSHBUTTONS

 

 

LED INDICATORS

 

 

 

 

Button 1

Button 2

DS1 (Red)

DS2 (Yellow)

DS3 (Green)

DS4 (Green)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STARTUP MODE

Action

 

 

flash

 

flash

 

flash

 

flash

 

 

 

 

 

 

 

 

 

Note 1

Indicators flash in sequence at .5 sec intervals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUN MODE

Names

 

 

HB

ECONO

Y1

Y2

Actions

 

 

flash

flash

steady

steady

 

 

 

 

 

 

 

 

 

 

Note 1 Heartbeat Indicator flashes to indicate proper operation of the control

 

 

 

Note 2

Econo indicator flashes to indicate free cooling being used

 

 

 

 

 

Note 3

Y1 and Y2 are on steady when a call thermostat Y1 and Y2 are closed

 

 

 

Note 4

ERROR - HB and Econo are on steady to indicate the presence of an error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Names

READ

ADV

SET NO

I/O NO

TEN'S

ONES OR

READ MODE

OR ON

OFF

 

 

 

 

 

 

 

 

 

Actions

Push

Push

flash, no

flash no

flash no

flash no

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 Push and release the READ button to enter Read Mode. The SET NO Indicator flashes once to indicate the setup point is selected for viewing

Note 2 Push and release ADV button repeatedly to advance to the desired setup point or I/O point Each time the ADV button is pushed, the SET NO flashes the point number until the desired I/O point is reached and then the I/O NO flashes the I/O point no.

Note 3 After the SET NO indicator identifies the desired point no, push and release the READ button to display the value in the TEN's and ONE's indicator (i.e., 5 flashes for a value of 5) or a steady TEN's indicator for an on and a steady ONE's for off.

To aid in counting, values of 5 are flashed in groups of 5 (i.e., 150 = 3 groups of fast 5 flashes) and then follow by balance in slow flashes (i.e., 7 = 5 quick flashes + 2 slow flashes)

Note 4 Setpoint values are displayed first followed by I/O values and then back to Setpoint values Red Set No LED displays Setup item numbers, and Yellow I/O LED displays I/O item no

Note 5 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit

MODE OF OPERATION

 

PUSHBUTTONS

 

LED INDICATORS

 

 

 

 

Button 1

 

Button 2

DS1 (Red)

DS2 (Yellow)

 

DS3 (Green)

 

DS4 (Green)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Names

ADJUST

 

ADV

SET NO

SETUP

 

TEN'S

 

ONES OR

SETUP MODE

 

 

OR ON

 

OFF

 

 

 

 

 

 

 

 

 

 

Actions

Hold/Push

 

Push

flash, no

steady

 

flash no

 

flash no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 Push and hold the ADJUST button until the SETUP indicator turns on.

 

 

 

Note 2 Push and release ADV button repeatedly to advance to the desired setup point.

 

 

Each time the ADV button is pushed, the SET NO flashes the point number and then displays

 

the current setting

 

 

 

 

 

 

 

 

 

Note 3

Once the current value has been displayed the TENS indicator will turn on steady and while it

 

on use the ADJUST button to enter the value. (i.e., push the button 4 times to enter 4)

 

Then wait for the ONES indicator to turn on and enter the ONES setting

 

 

 

 

Wait for indicator to turn off and then push read/adjust to check the setting

 

Note 4

Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit

 

 

 

 

 

 

 

 

 

 

 

 

 

Names

ADJUST

 

MAN

MAN

I/O NO

 

TEN'S

 

ONES OR

 

 

 

 

OR ON

 

OFF

 

MANUAL

 

 

 

 

 

 

 

 

 

Actions

Push

Hold/Push

steady

flash no

 

flash no

 

flash no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 Push and hold the MAN button until the MAN indicator turns on.

Note 2 Push and release MAN button repeatedly to advance to the desired I/O point. Each time the MAN button is pushed, the I/O NO flashes the I/O point number.

Note 3 After the desired I/O No is reached push and release the ADJUST to toggle the output on and off or open and closed

Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit

APPENDIX A — ECONOMI$ER+ LABEL

I/O POINTS

NO

I/O Points

UNITS

 

 

 

1

C1 Output

-

2

C2 Output

-

3

C3 Output

-

4

C4 Output

-

5

Economizer Damper Output

%

6

Supply Air temperature

F

7

Outside Air temperature

F

8

Return Air Temperature

F

9

Indoor Relative Humidity

%

10

Outdoor Relative Humidity

%

11

Indoor Air Quality

PPM

12

Remote Minimum Position

%

13

Y1 Status (next version)

-

14

Y2 Status (next version)

-

15

G Status (next version)

-

16

Occ Status (next version)

-

ALARM CODES

NO DESCRIPTION

1SAT sensor invalid

2RAT Sensor Invalid (only with changeover type 3&5)

3OAT Sensor Invalid

4ORH Sensor invalid (only with changeover type 3&4)

5IRH Sensor invalid (only with changeover type 5)

6IAQ Sensor Invalid (only if IAQ=1)

7Y2 on Y1 off

8Micro Fails E2 test

note 1 Micro Fails RAM test

note 2 Micro Fails ROM test

Note 1 DS1+DS3/DS2+D4 will alternately flash Note 2 DS1+DS2/DS3+D4 will alternately flash

Page 58
Image 58
Bryant 580F installation instructions Appendix a ECONOMI$ER+ Label, Startup Mode

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.