Carrier 19XR, XRV specifications Example of Time Schedule Operation Screen

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 20
Image 20
Fig. 19 — Example of Time Schedule

For Discrete Points — Press START or STOP to se- lect the desired state.

For Analog Points — Press INCREASE or DECREASE to select the desired value.

3. Press ENTER to register the new value.

NOTE: When overriding or changing metric values, it is nec- essary to hold down the softkey for a few seconds in order to see a value change, especially on kilopascal values.

To Remove an Override

1.On the point status table press NEXT or PREVIOUS to highlight the desired value.

2.Press SELECT to access the highlighted value.

3.Press RELEASE to remove the override and return the point to the PIC II’s automatic control.

Override Indication — An override value is indicated by “SUPVSR,” “SERVC,” or “BEST” flashing next to the point value on the STATUS table.

TIME SCHEDULE OPERATION (Fig. 19)

1.On the Menu screen, press SCHEDULE .

2.Press NEXT or PREVIOUS to highlight the desired schedule.

OCCPC01S — LOCAL Time Schedule

OCCPC02S — ICE BUILD Time Schedule

OCCPC03S — CCN Time Schedule

3.Press SELECT to view the desired time schedule.

4.Press NEXT or PREVIOUS to highlight the desired period or override to change.

5.Press SELECT to access the highlighted period or override.

6.a. Press INCREASE or DECREASE to change the time values. Override values are in one-hour increments, up to 4 hours.

b.Press ENABLE to select days in the day-of-week

fields. Press DISABLE to eliminate days from the period.

Fig. 19 — Example of Time Schedule

Operation Screen

20

Page 20
Image 20
Carrier 19XR, XRV specifications Example of Time Schedule Operation Screen