Carrier 19XR, XRV CVC/ICVC Primary and Secondary Messages and, G. Normal Run With Overrides

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 80
Image 80

Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

G. NORMAL RUN WITH OVERRIDES

STATE

PRIMARY

SECONDARY

ALARM MESSAGE

ADDITIONAL

MESSAGE

MESSAGE

PRIMARY CAUSE

CAUSE/REMEDY

 

120

RUN CAPACITY

HIGH CONDENSER

120->Condenser Pressure

Check for high condenser water temperatures.

 

LIMITED

PRESSURE

[VALUE] exceeded limit of [LIMIT]*.

Check setting in SETUP1.

121

RUN CAPACITY

HIGH MOTOR

121->Comp Motor Winding Temp

Check motor cooling lines.

 

LIMITED

TEMPERATURE

[VALUE] exceeded limit of [LIMIT]*.

Check for closed valves.

 

 

 

 

Check setting in SETUP1.

122

RUN CAPACITY

LOW EVAP

122->Evaporator Refrig Temp

Check refrigerant charge.

 

LIMITED

REFRIG TEMP

[VALUE] exceeded limit of [LIMIT]*.

Check for low entering cooler temperatures.

123

RUN CAPACITY

HIGH COMPRESSOR

123->Surge Prevention Override:

Check for high condenser water temperatures or

 

LIMITED

LIFT

Lift Too High For Compressor.

low suction temperature.

124

RUN CAPACITY

MANUAL GUIDE

124->Run Capacity Limited:

Target guide vane point has been forced in

 

LIMITED

VANE TARGET

Manual Guide Vane Target.

MAINSTAT screen. Release force to continue

 

 

 

 

normal operation.

125

RUN CAPACITY

LOW DISCHARGE

No messages.

Check oil charge.

 

LIMITED

SUPERHEAT

 

Check refrigerant charge.

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control has recorded at the time of the fault con- dition.

H. OUT-OF-RANGE SENSOR ALARMS

STATE

PRIMARY

SECONDARY

ALARM MESSAGE

ADDITIONAL

MESSAGE

MESSAGE

PRIMARY CAUSE

CAUSE/REMEDY

 

260

SENSOR

LEAVING CHILLED

260->Sensor Fault:

Check sensor resistance or voltage drop.

 

FAULT

WATER

Leaving Chilled Water

Check for proper wiring.

261

SENSOR

ENTERING CHILLED

261->Sensor Fault:

Check sensor resistance or voltage drop.

 

FAULT

WATER

Entering Chilled Water

Check for proper wiring.

262

SENSOR

CONDENSER

262->Sensor Fault:

Check sensor wiring.

 

FAULT

PRESSURE

Condenser Pressure

 

263

SENSOR

EVAPORATOR

263->Sensor Fault:

Check sensor wiring.

 

FAULT

PRESSURE

Evaporator Pressure

 

264

SENSOR

COMPRESSOR

264->Sensor Fault:

Check sensor resistance or voltage drop.

 

FAULT

BEARING TEMP

Comp Thrust Bearing Temp

Check for proper wiring.

265

SENSOR

COMPRESSOR

265->Sensor Fault:

Check sensor resistance or voltage drop.

 

FAULT

MOTOR TEMP

Comp Motor Winding Temp

Check for proper wiring.

266

SENSOR

COMP DISCHARGE

266->Sensor Fault:

Check sensor resistance or voltage drop.

 

FAULT

TEMP

Comp Discharge Temp

Check for proper wiring.

267

SENSOR

OIL SUMP TEMP

267->Sensor Fault:

Check sensor resistance or voltage drop.

 

FAULT

 

Oil Sump Temp

Check for proper wiring.

268

SENSOR

COMP OIL

268->Sensor Fault:

Check sensor wiring and accuracy.

 

FAULT

PRESS DIFF

Oil Pump Delta P

 

269

SENSOR

CHILLED WATER

269->Sensor Fault:

Check sensor wiring and accuracy.

 

FAULT

FLOW

Chilled Water Delta P

 

270

SENSOR

COND WATER

270->Sensor Fault:

Check sensor wiring and accuracy.

 

FAULT

FLOW

Cond Water Delta P

 

271

SENSOR

VFD SPEED SENSOR

271->Sensor Fault:

Check voltage input on terminals J6-1 and J6-2 on

 

FAULT

OUT OF RANGE

Check Actual VFD Speed Sensor

the ISM module. Check wiring.

273

SENSOR

VFD SPEED OUT OF

273->Sensor Fault:

Check VFD feedback 0-5 vac. Calibrate VFD

 

FAULT

RANGE

Check Actual VFD Speed Sensor

speed reference signal.

80

Page 80
Image 80
Carrier 19XR CVC/ICVC Primary and Secondary Messages and, Custom Alarm/Alert Messages with Troubleshooting Guides cont