Carrier XRV specifications 19XR Pumpout Unit Wiring Schematic, Optional Pumpout Unit

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 69
Image 69
Fig. 35 — 19XR Pumpout Unit Wiring Schematic

LEGEND

CContactor

FU — Fuse, 3 Amps

HP — High-Pressure Cutout

OL — Compressor Overload T’STAT — Internal Thermostat

Compressor Terminal

Contactor Terminal

Overload Terminal

Pumpout Unit Terminal

*Bimetal thermal protector imbedded in motor winding.

Fig. 35 — 19XR Pumpout Unit Wiring Schematic

OIL RETURN

LINE

CONNECTION

CONDENSER

REFRIGERANT

WATER

INLET VALVE

CONNECTIONS

 

Fig. 36 — Optional Pumpout Unit

Chillers with Storage Tanks — If the chiller has iso- lation valves, leave them open for the following procedures. The letter “C” describes a closed valve. See Fig. 17, 18, 29, and 30.

TRANSFER REFRIGERANT FROM PUMPOUT STOR- AGE TANK TO CHILLER

1.Equalize refrigerant pressure.

a.Use the PIC II terminate lockout function on the PUMPDOWN LOCKOUT screen, accessed from

the CONTROL TEST table to turn on the water pumps and monitor pressures.

If the chilled water and condenser water pumps are not controlled by the PIC II, these pumps must be started and stopped manually at the appropriate times during the refrig- erant transfer procedure.

b.Close pumpout unit valves 2, 4, 5, 8, and 10, and close chiller charging valve 7; open chiller isola- tion valves 11, 12, 13, and 14 (if present).

c.Open pumpout unit/storage tank valves 3 and 6, open chiller valves 1a and 1b.

 

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

12

13

14

 

 

CONDITION

 

 

C

 

C

C

 

C

C

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Follow Steps d and e carefully to prevent damage from freeze-up.

d.

Slowly open valve 5 to increase chiller pressure to

 

68 psig 35 psig (141 kPa) for HFC-134a. Feed

 

refrigerant slowly to prevent freeze up.

e.

Open valve 5 fully after the pressure rises above

 

the freeze point of the refrigerant. Open liquid line

 

valves 7 and 10 until refrigerant pressure

 

equalizes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

 

6

 

7

8

10

11

12

13

14

 

CONDITION

 

 

C

 

C

 

 

 

 

 

C

 

 

 

 

 

2. Transfer the remaining refrigerant.

 

 

 

 

 

 

 

 

 

a.

Close valve 5 and open valve 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

 

6

 

7

8

10

11

12

13

14

 

CONDITION

 

 

C

 

 

C

 

 

 

 

C

 

 

 

 

 

b.

Turn off the chiller water pumps using the CVC/

 

ICVC (or manually, if necessary).

 

 

 

 

 

 

c.

Turn off the pumpout condenser water, and turn on

 

the pumpout compressor to push liquid out of the

 

storage tank.

 

 

 

 

 

 

 

 

 

 

 

 

 

d.

Close liquid line valve 7.

 

 

 

 

 

 

 

 

 

 

 

e.

Turn off the pumpout compressor.

 

 

 

 

 

 

f.

Close valves 3 and 4.

 

 

 

 

 

 

 

 

 

 

 

 

g.

Open valves 2 and 5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

 

6

 

7

8

10

11

12

13

14

 

CONDITION

 

 

 

C

C

 

 

 

 

C

C

 

 

 

 

 

h.

Turn on the pumpout condenser water.

i.

Run the pumpout compressor until the pumpout

 

storage tank pressure reaches 5 psig (34 kPa)

 

(18 in. Hg [40 kPa absolute] if repairing the tank).

j.

Turn off the pumpout compressor.

 

 

 

 

 

 

k.

Close valves 1a, 1b, 2, 5, 6, and 10.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

1a

1b

2

3

4

5

 

6

 

7

8

10

11

12

13

14

 

CONDITION

C

C

C

C

C

C

C

C

C

C

 

 

 

 

l. Turn off pumpout condenser water.

69

Page 69
Image 69
Carrier XRV specifications 19XR Pumpout Unit Wiring Schematic, Optional Pumpout Unit