Carrier XRV Optional Pumpout System Electrical Data, Additional Miscellaneous Weights, 19EA47-748

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 97
Image 97
Table 18 — Optional Pumpout System

Table 18 — Optional Pumpout System

Electrical Data

MOTOR

CONDENSER

VOLTS-PH-Hz

MAX

LRA

CODE

UNIT

RLA

 

 

1

19EA47-748

575-3-60

3.8

23.0

4

19EA42-748

200/208-3-60

10.9

63.5

5

19EA44-748

230-3-60

9.5

57.5

6

19EA46-748

400/460-3-50/60

4.7

28.8

 

LEGEND

 

 

 

LRA — Locked Rotor Amps

RLA — Rated Load Amps

Table 19 — Additional Miscellaneous Weights

ITEM

Lb

Kg

CONTROL CABINET

30

14

UNIT-MOUNTED STARTER

500

227

OPTIONAL ISOLATION VALVES

115

52

UNIT MOUNTED VFD

1000

454

VFD — Variable Frequency Drive

 

 

Table 20 — Motor Voltage Code

MOTOR VOLTAGE CODE

Code

Volts

Frequency

60

200

60

61

230

60

62

380

60

63

416

60

64

460

60

65

575

60

66

2400

60

67

3300

60

68

4160

60

69

6900

60

50

230

50

51

346

50

52

400

50

53

3000

50

54

3300

50

55

6300

50