Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

I. CHILLER PROTECT LIMIT FAULTS (cont)

STATE

PRIMARY

SECONDARY

ALARM MESSAGE

ADDITIONAL

MESSAGE

MESSAGE

PRIMARY CAUSE

CAUSE/REMEDY

 

227

PROTECTIVE

OIL PRESS

227->Oil Pump Delta P

Check transducer wiring and accuracy.

 

LIMIT

SENSOR FAULT

[VALUE] exceeded limit of

Check power supply to pump.

 

 

 

[LIMIT]*.

Check pump operation.

 

 

 

 

Check transducer calibration.

228

PROTECTIVE

LOW OIL

228->Oil Pump Delta P

Check transducer wiring and accuracy.

 

LIMIT

PRESSURE

[VALUE] exceeded limit of

Check power supply to pump.

 

 

 

[LIMIT].*

Check pump operation.

 

 

 

 

Check oil level.

 

 

 

 

Check for partially closed service valves.

 

 

 

 

Check oil filters.

 

 

 

 

Check for foaming oil at start-up.

 

 

 

 

Check transducer calibration.

229

PROTECTIVE

LOW CHILLED

229->Low Chilled Water

Perform pump control test.

 

LIMIT

WATER FLOW

Flow; Check Delta P Config

Check transducer accuracy and wiring.

 

 

 

& Calibration

Check water valves.

 

 

 

 

Check transducer calibration.

230

PROTECTIVE

LOW CONDENSER

230->Low Condenser Water

Perform pump control test.

 

LIMIT

WATER FLOW

Flow; Check Delta P Config

Check transducer accuracy and wiring.

 

 

 

& Calibration

Check water valves.

 

 

 

 

Check transducer calibration.

231

PROTECTIVE

HIGH DISCHARGE

231->Comp Discharge

Check sensor resistance or voltage drop.

 

LIMIT

TEMP

Temp [VALUE] exceeded

Check for proper wiring.

 

 

 

limit of [LIMIT].*

Check for proper condenser flow and temperature.

 

 

 

 

Check for proper inlet guide vane and diffuser

 

 

 

 

actuator operation.

 

 

 

 

Check for fouled tubes or noncondensables in the

 

 

 

 

system.

232

PROTECTIVE

LOW REFRIGERANT

232->Evaporator Refrig

Check for proper refrigerant charge.

 

LIMIT

TEMP

Temp [VALUE] exceeded

Check float operation.

 

 

 

limit of [LIMIT]*.

Check for proper fluid flow and temperature.

 

 

 

 

Check for proper inlet guide vane operation.

233

PROTECTIVE

HIGH MOTOR

233->Comp Motor Winding

Check motor sensors wiring and accuracy.

 

LIMIT

TEMPERATURE

Temp [VALUE] exceeded

Check motor cooling line for proper operation, or

 

 

 

limit of [LIMIT]*.

restrictions.

 

 

 

 

Check for excessive starts within a short time span.

234

PROTECTIVE

HIGH BEARING

234->Comp Thrust Bearing

Check oil heater for proper operation.

 

LIMIT

TEMPERATURE

Temp [VALUE] exceeded

Check for low oil level, partially closed oil supply

 

 

 

limit of [LIMIT]*.

valves, clogged oil filters, etc.

 

 

 

 

Check the sensor wiring and accuracy.

235

PROTECTIVE

HIGH CONDENSER

235->Condenser Pressure

Check for high condenser water temperatures, low

 

LIMIT

PRESSURE

[VALUE] exceeded limit of

water flow, fouled tubes.

 

 

 

[LIMIT]*.

Check for division plate/gasket bypass.

 

 

 

 

Check for noncondensables.

 

 

 

 

Check transducer wiring and accuracy.

236

PROTECTIVE

CCN OVERRIDE

236->CCN Override Stop

CCN has signaled the chiller to stop. Reset and

 

LIMIT

STOP

while in LOCAL run mode

restart when ready. If the signal was sent by the

 

 

 

 

CVC/ICVC, release the stop signal on the STATUS01

 

 

 

 

table.

237

PROTECTIVE

SPARE SAFETY

237->Spare Safety Device

Spare safety input has tripped or factory installed

 

LIMIT

DEVICE

 

jumper is not present.

238

PROTECTIVE

EXCESSIVE

238->Compressor Surge:

Check condenser flow and temperatures.

 

LIMIT

COMPR SURGE

Check condenser water

Check surge protection configuration.

 

 

 

temp and flow

 

239

PROTECTIVE

TRANSDUCER

239->Transducer Voltage

 

 

LIMIT

VOLTAGE FAULT

Ref [VALUE] exceeded limit

 

 

 

 

of [LIMIT]*.

 

240

PROTECTIVE

LOW DISCHARGE

240->Check for Oil in

 

 

LIMIT

SUPERHEAT

Refrigerant or Overcharge

 

 

 

 

of Refrigerant

 

241

LOSS OF

WITH STARTER

241->Loss of Communica-

Check wiring to ISM.

 

COMMUNICATION

MODULE

tion With Starter.

 

242

LOSS OF

WITH CCM

242->Loss of Communica-

Check wiring to CCM.

 

COMMUNICATION

MODULE

tion With CCM.

 

243

POTENTIAL

EVAP PRESS/TEMP

243->Evaporator Refrig

Check for proper refrigerant charge.

 

FREEZE-UP

TOO LOW

Temp [VALUE] exceeded

Check float operation.

 

 

 

limit of [LIMIT]*.

Check for proper fluid flow and temperature.

 

 

 

 

Check for proper inlet guide vane operation.

244

POTENTIAL

COND PRESS/TEMP

244->Condenser Refrig

 

 

FREEZE-UP

TOO LOW

Temp [VALUE] exceeded

 

 

 

 

limit of [LIMIT]*.

 

245

PROTECTIVE

VFD SPEED

245->Actual VFD Speed

 

 

LIMIT

OUT OF RANGE

[VALUE] exceeded limit of

 

 

 

 

[LIMIT]*.

 

82

Page 82
Image 82
Carrier 19XR, XRV specifications Loss, Communication, Potential, Freeze-Up

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.