Carrier 19XR, XRV specifications Example of Status Screen

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 16
Image 16
Fig. 16 — Example of Status Screen

Press QUIT to leave the selected decision or field with- out saving any changes.

Press ENTER to leave the selected decision or field and save changes.

Press NEXT to scroll the cursor bar down in order to highlight a point or to view more points below the cur- rent screen.

Press PREVIOUS to scroll the cursor bar up in order to highlight a point or to view points above the current screen.

Press SELECT to view the next screen level (high- lighted with the cursor bar), or to override (if allowable) the highlighted point value.

Press EXIT to return to the previous screen level.

Press INCREASE or DECREASE to change the high- lighted point value.

TO VIEW STATUS (Fig. 16) — The status table shows the actual value of overall chiller status such as CONTROL MODE, RUN STATUS, AUTO CHILLED WATER RESET, and REMOTE RESET SENSOR.

1.On the menu screen, press STATUS to view the list of point status tables.

2.Press NEXT or PREVIOUS to highlight the desired status table. The list of tables is:

•MAINSTAT — Overall chiller status

•STARTUP — Status required to perform start-up of chiller

•COMPRESS — Status of sensors related to the compressor

•HEAT_EX — Status of sensors related to the heat exchangers

•POWER — Status of motor input power

•ISM_STAT — Status of motor starter

•CVC_PSWD — Service menu password forcing access screen

•ICVC_PSWD — Service menu password forcing access screen

3.Press SELECT to view the desired point status table.

4. On the point status table, press NEXT or PREVIOUS until the desired point is displayed on the screen.

 

 

 

19XR_II MAINSTAT

 

POINT STATUS

 

 

 

Control Mode

 

 

OFF

 

 

 

Run Status

 

 

Ready

 

 

 

Start Inhibit Timer

 

 

0.0 Min

 

 

 

Occupied?

 

 

 

NO

 

 

 

System Alert/Alarm

 

NORMAL

 

 

 

Chiller Start/Stop

 

 

STOP

 

 

 

 

 

 

 

 

Remote Start Contact

 

 

Open

 

 

 

Temperature Reset

 

 

0.0 F

 

 

 

Control Point

 

 

44.0 F

 

 

 

Chilled Water Temp

 

 

44.6 F

 

 

 

Active Demand Limit

100%

 

 

 

Average Line Current

0.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 16 — Example of Status Screen

OVERRIDE OPERATIONS

To Override a Value or Status

1.From any point status screen, press NEXT or PREVIOUS to highlight the desired value.

2.Press SELECT to select the highlighted value. Then:

16

Page 16
Image 16
Carrier 19XR, XRV specifications Example of Status Screen