Carrier XRV, 19XR specifications CVC/ICVC Display Data cont

Models: 19XR XRV

1 140
Download 140 pages 13.24 Kb
Page 29
Image 29
Manual background

Table 2 — CVC/ICVC Display Data (cont)

EXAMPLE 15 — NET_OPT DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight

4.Press SELECT .

5.Scroll down to highlight

6.Press SELECT .

EQUIPMENT CONFIGURATION .

NET_OPT .

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Loadshed Function

 

 

 

 

Group Number

0-99

 

ldsgrp

0

Demand Limit Decrease

0-60

%

ldsdelta

20

Maximum Loadshed Time

0-120

MIN

maxldstm

60

CCN Occupancy Config:

 

 

 

 

Schedule Number

3-99

 

occpcxxe

3

Broadcast Option

0-1

DSABLE/ENABLE

occbrcst

DSABLE

Alarm Configuration

 

 

 

 

Re-Alarm Time

0-1440

MIN

 

30

Alarm Routing

0-1

 

 

10000000

NOTE: No variables are available for CCN read or write operation.

EXAMPLE 16 — ISM_CONF DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight

4.Press SELECT .

ISM (STARTER) CONFIG DATA .

5. Enter password (4444 Factory Default).

6.Scroll down to highlight

7.Press SELECT .

ISM_CONF .

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Starter Type

0-2

 

starter

1

(0 = Full, 1 = Red, 2 = SS/VFD)

 

 

 

 

Motor Rated Line Voltage

200-13200

VOLTS

v_fs

460

Volt Transformer Ratio:1

1-35

 

vt_rat

1

Overvoltage Threshold

105-115

%

overvolt

115

Undervoltage Threshold

85-95

%

undvolt

85

Over/Under Volt Time

1-10

SEC

uvuntime

5

Voltage % Imbalance

1-10

%

v_unbal

10

Voltage Imbalance Time

1-10

SEC

v_time

5

Motor Rated Load Amps

10-5000

AMPS

a_fs

200

Motor Locked Rotor Trip

100-60000

AMPS

motor_lr

1000

Locked Rotor Start Delay

1-10

cycles

lrdelay

5

Starter LRA Rating

100-60000

AMPS

start_lr

2000

Motor Current CT Ratio:1

3-1000

 

ct_turns

100

Current % Imbalance

5-40

%

c_unbal

15

Current Imbalance Time

1-10

SEC

c_time

5

Grnd Fault CT’s?

0-1

NO/YES

gf_phase

YES

Ground Fault CT Ratio:1

150

 

gf_ctr

150

Ground Fault Current

1-25

AMPS

gf_amps

15

Ground Fault Start Delay

1-20

cycles

gf_delay

10

Ground Fault Persistence

1-10

cycles

gf_pers

5

Single Cycle Dropout

0/1

DSABLE/ENABLE

cycdrop

DSABLE

Frequency = 60 Hz? (No = 50)

0/1

NO/YES

freq

YES

Line Frequency Faulting

0/1

DSABLE/ENABLE

freq_en

DSABLE

29

Page 29
Image 29
Carrier XRV, 19XR specifications CVC/ICVC Display Data cont