Application Procedure

Section 4-3

4-3 Connections

4-3-1 Types of Connection

Port connections for Host Link communications are shown in the following table.

Up to 32 nodes can be connected for 1:N connections.

Port

Configura-

Schematic diagram

 

tion

 

RS-232C

1:1

 

 

 

RS-232C

 

RS-232C

NT-AL001-E

RS-422A/485 NT-AL001-E

RS-232CResistance ON

Resistance ON

5-V power

 

RS-232C

1:N

RS-422A/485

 

 

RS-232C

 

 

 

 

NT-AL001-E

 

NT-AL001-E

 

Resistance ON

 

 

Resistance ON

RS-232C

RS-232C

RS-232C

 

5-V power

 

 

 

 

 

 

 

 

RS-422A/485

1:1

 

 

 

 

RS-232C NT-AL001-ERS-422A/485

 

 

Resistance ON

 

Resistance ON

 

5-V power

 

 

 

 

RS-422A/485

1:N

RS-422A

3G2A9-AL001

 

RS-232C

/485

 

 

 

 

 

RS-422A

 

 

NT-AL001-E

 

/485

 

 

 

 

 

 

Resistance ON

 

 

 

 

5-V power

 

 

 

 

 

 

 

Resistance ON

Note 1. Four-wire connections must be used for RS-422A/485 connections with Host Link communications.

2.“Resistance ON” indicates the terminating resistance must be turned ON.

3.“5-V power” indicates that a 5-V power supply is required for the Link Adapt- er. Refer to the Link Adapter manual for details. A 5-V power supply is not required for a Link Adapter connected to a Serial Communications Board because power is supplied from pin 6 of the connector.

4.The maximum cable length for RS-232C is 15 m.

Connection Examples

The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 2-3 Wiring for actual wiring methods.

39