Omron CQM1H-SCB41 operation manual Appendix F, E5ZE Temperature Controller Write Protocol

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 215
Image 215

Appendix F

E5ZE Temperature Controller Write Protocol

The E5ZE Temperature Controller Write Protocol writes and controls various settings in remote mode for the Tem- perature Controller connected via a RS-232C or RS-422A/485 cable from the PC via the Serial Communications Board.

Note 1. Negative values cannot be written. All values must be set as unsigned BCD.

2. All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks.

Structure of the Protocol

The following table shows the structure of the E5ZE Temperature Controller Write Protocol.

Sequence

Communications sequence name

Function

Ladder interface

No.

 

 

 

 

 

 

Send word

Receive

 

 

 

 

 

 

allocation

word

 

 

 

 

allocation

 

 

 

 

 

150

Write set point (setting unit 1)

Writes the set points using a setting unit of 1.

Yes

No

 

 

 

 

 

151

Write set point (setting unit 0.1)

Writes the set points using a setting unit of 0.1.

Yes

No

 

 

 

 

 

152

Write proportional band, integral time, and

Writes the proportional bands, integral times,

Yes

No

 

derivative time

and derivative times.

 

 

 

 

 

 

 

153

Write control period

Writes the control periods.

Yes

No

 

 

 

 

 

154

Write output mode

Writes the output modes.

Yes

No

 

 

 

 

 

155

Write alarm mode

Writes the alarm modes.

Yes

No

 

 

 

 

 

156

Write alarm temperature (setting unit 1)

Writes the alarm temperatures using a setting

Yes

No

 

 

unit of 1.

 

 

 

 

 

 

 

157

Write alarm temperature (setting unit 0.1)

Writes the alarm temperatures using a setting

Yes

No

 

 

unit of 0.1.

 

 

 

 

 

 

 

158

Write hysteresis

Writes the hysteresis.

Yes

No

 

 

 

 

 

159

Start autotuning

Starts autotuning.

Yes

No

 

 

 

 

 

160

Cancel autotuning

Cancels autotuning.

Yes

No

 

 

 

 

 

161

Write setting unit

Writes the setting units.

Yes

No

 

 

 

 

 

162

Write input shift value

Writes the input shift values.

Yes

No

 

 

 

 

 

163

Write manual reset value

Writes the manual reset values.

Yes

No

 

 

 

 

 

164

Write ramp value

Writes the ramp values.

Yes

No

 

 

 

 

 

165

Write manual output value

Writes the manual output values.

Yes

No

 

 

 

 

 

166

Write output value limit

Writes the output value limits.

Yes

No

 

 

 

 

 

167

Write output value change rate limit

Write output value change rate limits.

Yes

No

 

 

 

 

 

168

Save settings

Saves settings.

Yes

No

 

 

 

 

 

169

Initialize settings

Initializes settings.

Yes

No

 

 

 

 

 

170

Write HB alarm and HS alarm valid chan-

Writes the HB alarm and HS alarm valid chan-

Yes

No

 

nels

nels.

 

 

 

 

 

 

 

171

Write heater burnout and SSR failure

Writes the heater burnout and SSR failure

Yes

No

 

detection currents

detection currents.

 

 

 

 

 

 

 

172

Write dead band/overlap band

Writes the dead bands/overlap bands.

Yes

No

 

 

 

 

 

173

Write cooling coefficient

Writes the cooling coefficients.

Yes

No

 

 

 

 

 

174

Start control

Starts temperature control.

Yes

No

 

 

 

 

 

175

Stop operation or control

Stops temperature control or manual operation.

Yes

No

 

 

 

 

 

176

Start manual operation

Starts manual operation.

Yes

No

Note Ladder Interface Settings

 

YES:

User settings are required for the 2nd or 3rd operands of PMCR.

NO:

Send word allocation:

Set the constant 0000 for the 2nd operand (S).

 

Receive word allocation:

Set a dummy word (e.g., DM0000) address for the 3rd operand (D).

209

Page 215
Image 215
Omron CQM1H-SCB41 operation manual Appendix F, E5ZE Temperature Controller Write Protocol