Omron CQM1H-SCB41 operation manual Write Output Mode Sequence No, Write Alarm Mode Sequence No

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 220
Image 220
Unit No.
Alarm 1 set code
Alarm 2 set code
Alarm 1 set code
Alarm 2 set code
Alarm 1 set code
alarm 2 set code

E5ZE Temperature Controller Write Protocol

Appendix F

 

 

 

Write Output Mode (Sequence No. 154)

Writes the output mode (normal/reverse).

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

(Undefined)

Write code

 

 

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0003

(fixed)

 

(4 digits BCD)

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to 0F

 

 

 

+2

Write code (2 digits Hex)

00 to FF

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Alarm Mode (Sequence No. 155)

Writes the alarm modes for alarm 1 and alarm 2.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

send data

+1

 

 

 

 

 

 

+2

 

 

 

 

 

 

+3

 

 

+4

 

 

 

 

+5

 

 

 

 

 

~

 

+16

 

 

+17

 

 

 

 

 

 

Number of send data words

(Undefined)

(Undefined)

(Undefined)

(Undefined)

(Undefined)

~

(Undefined)

(Undefined)

Channel 0

Channel 1

Channel 7

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0018

(fixed)

 

(4 digits BCD)

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to 0F

 

 

 

+2

Channel 0

00 to 0C

 

Alarm 1 set code (2 digits Hex)

 

 

 

 

 

+3

Channel 0

00 to 0C

 

Alarm 2 set code (2 digits Hex)

 

 

 

 

 

+4

Channel 1

00 to 0C

 

Alarm 1 set code (2 digits Hex)

 

 

 

 

 

+5

Channel 1

00 to 0C

 

Alarm 2 set code (2 digits Hex)

 

 

 

 

 

 

 

D

 

 

 

D

 

 

 

D

 

 

 

 

 

+16

Channel 7

00 to 0C

 

Alarm 1 set code (2 digits Hex)

 

 

 

 

 

+17

Channel 7

00 to 0C

 

Alarm 2 set code (2 digits Hex)

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

214

Page 220
Image 220
Omron CQM1H-SCB41 operation manual Write Output Mode Sequence No, Write Alarm Mode Sequence No