Image 110

Using No-protocol Communications

Section 6-2

6-2 Application Procedure

1, 2, 3... 1. Turn OFF the power supply to the PC.

2.Mount the Board.

3.Connections

Connect the external devices using RS-232C or RS-422 cables. The TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port.

The CPU Unit can be connected to a Programming Console, the CX-Pro- grammer, or the CX-Protocol as required.

4.Turn ON power.

5.Set the PC Setup settings for the Serial Communications Board.

Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6500 and DM 6559.

Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the set- tings. They will be updated automatically as soon as they are changed.

The following table shows the settings for using STX as the start code, CR+LF as the end code, and no transmission delay.

Port 1

Port 2

Bit(s)

Setting

Function

 

 

 

 

 

DM 6555

DM 6550

00 to 03

0 Hex

Standard port settings

 

 

 

 

(1 start bit, 7-bit data, even parity,

 

 

 

 

2 stop bits, 9,600 bps)

 

 

 

 

 

 

 

04 to 11

---

Not used.

 

 

 

 

 

 

 

12 to 15

1 Hex

Serial communications mode

 

 

 

 

No-protocol

DM 6556

DM 6551

00 to 07

00 Hex

Baud rate setting disabled.

 

 

 

 

 

 

 

08 to 15

00 Hex

Frame format setting disabled.

 

 

 

 

 

DM 6557

DM 6552

00 to 15

0000

Transmission delay: 0 ms

 

 

 

(BCD)

0000 to 9999 (BCD): Set in units

 

 

 

 

of 10 ms

 

 

 

 

 

DM 6558

DM 6553

00 to 07

---

Not used.

 

 

 

 

 

 

 

08 to 11

1 Hex

Start code enabled

 

 

 

 

 

 

 

12 to 15

2 Hex

End code enabled as CR+LF

 

 

 

 

0: Disable (number of receive

 

 

 

 

bytes set)

 

 

 

 

1: Set (specified end code)

 

 

 

 

2: CR, LF

 

 

 

 

 

DM 6559

DM 6554

00 to 07

02 Hex

Start code: STX

 

 

 

 

 

 

 

08 to 15

00 Hex

Number of receive bytes

 

 

 

 

(Disabled when end code is set.)

6.Write and execute the ladder program. Use TXD(––) to send data to an ex- ternal device and RXD(––) to receive data from an external device.