Omron CQM1H-SCB41 operation manual Write HB and HS Alarm Valid Channels Sequence No

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 230
Image 230

E5ZE Temperature Controller Write Protocol

Appendix F

 

 

 

Write HB and HS Alarm Valid Channels (Sequence No. 170)

Writes the valid or invalid channels of HB alarm and HS alarm.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

send data

+1

 

 

+2

Number of send data words

(Undefined)

Unit No.

 

 

(Undefined)

Write code

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0003

(fixed)

 

(4 digits BCD)

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to 0F

 

 

 

+2

Write code (2 digits Hex)

00 to FF

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Heater Burnout and SSR Failure Detection Current (Sequence No. 171)

Writes the currents for detecting heater burnouts and SSR failures.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

 

send data

 

 

 

 

 

 

+1

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+2

 

Heater burnout detection current

 

 

 

 

 

 

 

+3

 

SSR failure detection current

 

 

+4

 

Heater burnout detection current

 

 

 

 

 

 

 

 

 

 

 

 

+5

 

SSR failure detection current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

~

 

 

 

 

 

 

 

+16

 

Heater burnout detection current

 

 

 

+17

 

SSR failure detection current

 

 

 

 

 

 

 

Channel 0

Channel 1

Channel 7

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0018 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to 0F

 

 

 

+2

Channel 0

0000 to 0500

 

Heater burnout detection current

 

 

(4 digits BCD)

 

 

 

 

+3

Channel 0

0000 to 0500

 

SSR failure detection current

 

 

(4 digits BCD)

 

 

 

 

+4

Channel 1

0000 to 0500

 

Heater burnout detection current

 

 

(4 digits BCD)

 

 

 

 

+5

Channel 1

0000 to 0500

 

SSR failure detection current

 

 

(4 digits BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+16

Channel 7

0000 to 0500

 

Heater burnout detection current

 

 

(4 digits BCD)

 

 

 

 

+17

Channel 7

0000 to 0500

 

SSR failure detection current

 

 

(4 digits BCD)

 

Receive Data Word Allocation (3rd Operand of PMCR)