Node No.
Subaddress
SID

CompoWay/F Master Protocol

Appendix B

 

 

 

General-purpose Send with No Conversion and with Response (Sequence No. 604)

This sequence sends the specified data beginning with the subaddress and SID to the specified Unit. The re- sponse is stored starting at the specified word. No conversions are performed on the send and receive data.

Send Data Word Allocation (2nd Operand of PMCR(260))

First word of

+0

send data

+1

 

 

+2

 

+3

 

+4

 

+5

Number of send data words

(Undefined)

(Undefined)

(Undefined)

Number of send bytes

Send data

Offset

Contents (data format)

Data

 

 

 

 

+0

Number of send data words

0006 to 0128

 

(4 digits BCD)

 

 

 

 

 

 

+1

Always 00 Hex

Node No. (2 digits

00 to 99

 

 

BCD)

 

 

 

 

 

+2

MRC

Subaddress (2

Specify the subaddress of the device being

 

(2 digits Hex)

digits Hex)

communicated with.

 

 

 

 

+3

Always 00 Hex

SID (1 digit Hex)

Set the service ID of the required service

 

 

 

(e.g., retries).

 

 

 

 

+4

Number of send bytes (4 digits BCD)

Number of data bytes from the MCR until

 

 

 

the byte just before the ETX.

 

 

 

0 to 490 decimal

 

 

 

 

+5

Send data

 

The data specified in hexadecimal here is

on

 

 

not converted and the number of bytes

+0

+1

 

specified in S+4 is sent.

 

 

 

 

+2

+3

 

 

 

 

 

 

 

+4

+5

 

 

 

 

 

 

+6 etc.

 

 

Receive Data Word Allocation (3rd Operand of PMCR(260))

Receive data

+0

storage words

+1

 

 

+2

Number of receive data words

Response code

Response data

Offset

Contents (data format)

Data

 

 

 

 

+0

Number of receive data words

0003 to 0128

 

(4 digits BCD)

 

 

 

 

 

 

+1

Response code (4 digits Hex)

The response code will be stored in

 

 

 

hexadecimal form.

 

 

 

 

+2

Receive data

 

The data from just after the response code

on

 

 

until just before the ETX is stored here

+0

+1

 

without conversion.

 

 

 

 

+2

+3

 

 

 

 

 

 

 

+4

+5

 

 

 

 

 

 

+6 etc.

 

 