Omron CQM1H-SCB41 operation manual Host Link Commands, Header code PC mode Name

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 63
Image 63

Application ProcedureSection 4-4

4-4-3

Host Link Commands

 

 

 

 

The Host Link commands listed in the following table can be sent to the CQM1H

 

 

 

for Host Link communications. Refer to the CQM1H-series Programming Manu-

 

 

 

al for details.

 

 

 

 

 

 

Header code

 

PC mode

 

Name

 

 

 

 

 

 

 

 

RUN

MON

PRG

 

 

 

 

 

 

 

RR

 

Valid

Valid

Valid

IR/SR AREA READ

 

 

 

 

 

 

RL

 

Valid

Valid

Valid

LR AREA READ

 

 

 

 

 

 

RH

 

Valid

Valid

Valid

HR AREA READ

 

 

 

 

 

 

RC

 

Valid

Valid

Valid

TC PV READ

 

 

 

 

 

 

RG

 

Valid

Valid

Valid

TC STATUS READ

 

 

 

 

 

 

RD

 

Valid

Valid

Valid

DM AREA READ

 

 

 

 

 

 

RE

 

Valid

Valid

Valid

EM AREA READ

 

 

 

 

 

 

RJ

 

Valid

Valid

Valid

AR AREA READ

 

 

 

 

 

 

WR

 

Not valid

Valid

Valid

IR/SR AREA WRITE

 

 

 

 

 

 

WL

 

Not valid

Valid

Valid

LR AREA WRITE

 

 

 

 

 

 

WH

 

Not valid

Valid

Valid

HR AREA WRITE

 

 

 

 

 

 

WC

 

Not valid

Valid

Valid

TC PV WRITE

 

 

 

 

 

 

WG

 

Not valid

Valid

Valid

TC STATUS WRITE

 

 

 

 

 

 

WD

 

Not valid

Valid

Valid

DM AREA WRITE

 

 

 

 

 

 

WE

 

Not valid

Valid

Valid

EM AREA WRITE

 

 

 

 

 

 

WJ

 

Not valid

Valid

Valid

AR AREA WRITE

 

 

 

 

 

 

R#

 

Valid

Valid

Valid

SV READ 1

 

 

 

 

 

 

R$

 

Valid

Valid

Valid

SV READ 2

 

 

 

 

 

 

R%

 

Valid

Valid

Valid

SV READ 3

 

 

 

 

 

 

W#

 

Not valid

Valid

Valid

SV CHANGE 1

 

 

 

 

 

 

W$

 

Not valid

Valid

Valid

SV CHANGE 2

 

 

 

 

 

 

W%

 

Not valid

Valid

Valid

SV CHANGE 3

 

 

 

 

 

 

MS

 

Valid

Valid

Valid

STATUS READ

 

 

 

 

 

 

SC

 

Valid

Valid

Valid

STATUS WRITE

 

 

 

 

 

 

MF

 

Valid

Valid

Valid

ERROR READ

 

 

 

 

 

 

KS

 

Not valid

Valid

Valid

FORCED SET

 

 

 

 

 

 

KR

 

Not valid

Valid

Valid

FORCED RESET

 

 

 

 

 

 

FK

 

Not valid

Valid

Valid

MULTIPLE FORCED SET/RESET

 

 

 

 

 

 

KC

 

Not valid

Valid

Valid

FORCED SET/RESET CANCEL

 

 

 

 

 

 

MM

 

Valid

Valid

Valid

PC MODEL READ

 

 

 

 

 

 

TS

 

Valid

Valid

Valid

TEST

 

 

 

 

 

 

RP

 

Valid

Valid

Valid

PROGRAM READ

 

 

 

 

 

 

WP

 

Not valid

Not valid

Valid

PROGRAM WRITE

 

 

 

 

 

 

QQ

 

Valid

Valid

Valid

COMPOUND COMMAND

 

 

 

 

 

 

XZ

 

Valid

Valid

Valid

ABORT (command only)

 

 

 

 

 

 



 

Valid

Valid

Valid

INITIALIZE (command only)

 

 

 

 

 

 

EX

 

Valid

Valid

Not valid

TXD RESPONSE (response only)

 

 

 

 

 

 

IC

 

---

---

---

Undefined command (response only)

51

Page 63
Image 63
Omron CQM1H-SCB41 operation manual Host Link Commands, Header code PC mode Name