E5jJ Temperature Controller Protocol

 

 

 

 

 

 

Appendix G

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Receive data

 

+0

Number of receive data words

 

 

 

storage words

 

 

 

 

 

 

 

 

 

+1

(Undefined)

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+2

(Undefined)

Alarm 1 type

Alarm 2 type

Input type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

 

Contents (data format)

 

 

Data

 

 

 

 

 

 

 

 

 

 

 

 

+0

 

Number of receive data words

 

0003

 

 

 

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+1

 

Status (2 digits Hex)

 

00 to 99

 

 

 

 

 

 

 

 

 

 

+2

 

Alarm 1 type (1 digit Hex)

 

0 to 9

 

 

 

 

 

Alarm 2 type (1 digit Hex)

 

0 to 9

 

 

 

 

 

Input type (1 digit BCD)

 

0 to 9

 

General-purpose Write (Sequence No. 216)

Writes the parameter specified by setting a header code.

Send Data Word Allocation (2nd Operand of PMCR)

First word of send +0

data

+1

+2

+3

+4

Number of send data words

 

 

 

(Undefined)

 

Unit No.

 

 

Header code (ASC)

 

 

(Undefined)

 

Data code

 

 

 

Send data

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0005 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Header code (two ASCII characters)

Header codes that can be set

 

 

MB, WS, W%, WW, WB, WN, WV

 

 

 

+3

Data code (2 digits BCD)

01 to 02

 

 

 

+4

Write data (4 digits BCD)

0000 to 9999

Receive Data Word Allocation (3rd Operand of PMCR)

None.

General-purpose Read (Sequence No. 217)

Reads the parameter specified by setting a header

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

send data

+1

 

 

+2

 

+3

Number of send data words

(Undefined)

Unit No.

 

 

Header code (ASC)

 

 

(Undefined)

Data code

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0004 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Header code (two ASCII characters)

Header codes that can be set

 

 

RS, R%, RW, RB, RN, RV, RO

 

 

 

+3

Data code (2 digits BCD)

01 to 02

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

storage words

+1

 

Number of receive data words

Receive data

241

Page 246
Image 246
Omron CQM1H-SCB41 operation manual 241