V600/V620 ID Controller Protocol

 

Appendix M

 

 

 

 

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

 

 

 

 

 

+0

Number of receive data

0002 to 0062

 

 

 

 

words (4 digits BCD)

 

 

 

 

 

 

 

 

 

 

+1 to +61

Read data (Hexadecimal)

Number of read bytes stored in hexadecimal

 

 

 

 

 

data

 

 

 

 

 

 

 

Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the re- ceive data words.

Read (Hexadecimal/2) (Sequence No. 505)

This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head.

Send Data Word Allocation (2nd Operand of PMCR)

First word of send +0

data+1

+2

+3

+4

+5

+6

+7

+8

+9

Number of send data words

Number of Heads

(Undefined)

 

Unit No.

 

 

 

(Undefined)

 

Head CH No.

 

 

Leading address No.

 

 

(Undefined)

Read bytes

 

 

 

(Undefined)

 

Unit No.

 

 

 

(Undefined)

 

Head CH No.

 

 

Leading address No.

 

 

(Undefined)

Read bytes

 

 

 

CH 1

CH 2

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0006 to 0010

 

(4 digits BCD)

 

 

 

 

+1

Number of Heads

0001 to 0002

 

(4 digits BCD)

 

 

 

 

+(4(N–1)+2)

Unit No. (2 digits BCD)

Arbitrary (However, there is a limit for the

 

 

maximum Unit No. depending on the model)

 

 

 

+(4(N–1)+3)

R/W Head CH No.

R/W Head CH 1 designation: 1

 

(1 digit BCD)

R/W Head CH 2 designation: 2

 

 

 

 

The CD1D must be set to 1.

 

 

 

+(4(N–1)+4)

Leading address No.

0000 to FFFF

 

(4 digits Hexadecimal)

 

 

 

 

+(4(N–1)+5)

Read bytes

01 to 3C (1 to 60 bytes)

 

(2 digits Hexadecimal)

 

 

 

 

N: Number of Heads

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

Number of receive data words

 

storage words

+1

Read data

 

 

 

 

 

 

 

 

 

~

~

 

 

 

 

 

+30

Read data

 

 

+31

Not used

 

 

 

 

 

 

~

~

 

+60

Not used

 

 

+61

Read data

 

 

 

 

 

 

 

 

 

~

~

 

 

 

 

 

+90

Read data

 

 

 

 

 

CH 1

CH 2

379

Page 382
Image 382
Omron CQM1H-SCB41 operation manual Read Hexadecimal/2 Sequence No