Appendix N

Hayes Modem AT Command Protocol

The Hayes Modem AT Command Protocol is used to make various settings or control remotely a Hayes modem connected to the Serial Communications Board via RS-232C cable.

Protocol Configuration

The configuration of the Hayes Modem AT Command Protocol is shown below.

Sequence

Communications

Function

Ladder interface

No.

sequence name

 

 

 

 

Send word

Receive word

 

 

 

 

 

 

allocation

allocation

550

Initialize modem

Initializes the modem connected to the

Yes

No

 

(general-purpose)

Serial Communications Board. The

 

 

 

 

initialization command is set in the words

 

 

 

 

specified for the second operand of

 

 

 

 

PMCR.

 

 

 

 

 

 

 

560

Initialize modem

Initializes certain OMRON Modems.

No

No

570

(specialized)

 

 

 

580

 

 

 

 

 

 

 

 

 

561

Dial

Dials from the modem connected to the

Yes

No

571

 

Serial Communications Board. AT

 

 

581

 

commands and telephone numbers are set

 

 

 

 

set in the words specified for the second

 

 

 

 

operand of PMCR. This sequence can be

 

 

 

 

used only for certain OMRON modems.

 

 

 

 

 

 

 

552

Password

After the line is connected, the password

Yes

No

 

 

sent from the other exchange is verified to

 

 

 

 

confirm that the line is connected to the

 

 

 

 

desired exchange. The normal value of a

 

 

 

 

password is set in the words specified for

 

 

 

 

the second operand of PMCR.

 

 

 

 

 

 

 

553

Data send/receive

Sends arbitrary data to the exchange

Yes

Yes

 

(general purpose

which the line is connected. Send data is

 

 

 

sequence)

set in the words specified for the second

 

 

 

 

operand of PMCR. Receive data is stored

 

 

 

 

in the words specified for the third operand

 

 

 

 

of PMCR.

 

 

 

 

 

 

 

554

Escape

Shifts the modem to escape mode (the

No

No

 

 

condition in which command input is

 

 

 

 

available during data communications).

 

 

 

 

The escape code is fixed to “+++”

 

 

 

 

 

 

 

555

Hang up

After shifting to escape mode, the line is

No

No

 

 

disconnected.

 

 

 

 

 

 

 

562

Initialize and dial

Executes continuously from initialization to

Yes*

No

572

 

dialling operations for certain OMRON

 

 

582

 

Modems.

 

 

 

 

 

 

 

590

Escape to hang up

Executes continuously from shifting to the

No

No

 

 

escape mode to hanging up.

 

 

Note 1.

Ladder Interface Settings

 

 

YES:

User settings are required for the 2nd and 3rd operands of PMCR.

 

NO:

Send word allocation:

Set a dummy word address for the 3rd operand (D).

 

 

Receive word allocation:

Set the constant 0000 for the 2rd operand (S).

2.

For details about dialling, refer to sequences 561, 571 and 581.