E5jK Digital Controller Write Protocol

Appendix D

 

 

 

Write Level 1 Parameter 2 (Sequence No. 067)

Writes parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) to multiple units.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

 

send data

 

 

 

 

 

 

 

+1

 

Number of units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+2

 

(Undefined)

 

Unit No.

 

 

 

 

 

 

 

 

 

 

+3

 

Cooling coefficient

 

 

 

 

 

 

 

 

 

 

+4

 

Dead band

 

 

 

 

 

 

 

 

 

 

 

+5

 

Manual reset value

 

 

 

 

 

 

 

 

 

+6

 

Hysteresis (heating)

 

 

+7

 

Hysteresis (cooling)

 

 

+8

 

Control period (heating)

 

 

 

 

 

 

+9

 

Control period (cooling)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

 

~

 

+58

 

(Undefined)

 

Unit No.

 

 

 

 

 

 

 

 

 

 

+59

 

Cooling coefficient

 

 

 

 

 

 

 

 

 

 

+60

 

Dead band

 

 

 

 

 

 

 

 

 

 

 

+61

 

Manual reset value

 

 

 

 

 

 

 

 

 

+62

 

Hysteresis (heating)

 

 

 

 

 

 

 

 

 

+63

 

Hysteresis (cooling)

 

 

+64

 

Control period (heating)

 

 

+65

 

Control period (cooling)

 

1st unit

8th unit (max.)

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

Number of units  8 + 2

 

(4 digits BCD)

 

 

 

 

+1

Number of units (4 digits BCD)

0001 to 0008

 

 

 

+2

1st unit

00 to 31

 

Unit No. (2 digits BCD)

 

 

 

 

+3

1st unit

0001 to 9999

 

Cooling coefficient (4 digits BCD)

 

 

 

 

+4

1st unit

0000 to 9999

 

Dead band (4 digits BCD)

 

 

 

 

+5

1st unit

0000 to 1000

 

Manual reset value (4 digits BCD)

 

 

 

 

+6

1st unit

0001 to 9999

 

Hysteresis (heating)

 

 

(4 digits BCD)

 

 

 

 

+7

1st unit

0001 to 9999

 

Hysteresis (cooling)

 

 

(4 digits BCD)

 

 

 

 

+8

1st unit

0001 to 0099

 

Control period (heating)

 

 

(4 digits BCD)

 

 

 

 

+9

1st unit

0001 to 0099

 

Control period (cooling)

 

 

(4 digits BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+65

8th unit

0001 to 0099

(max.)

Control period (cooling)

 

 

(4 digits BCD)

 

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

179

Page 186
Image 186
Omron CQM1H-SCB41 operation manual Write Level 1 Parameter 2 Sequence No