Omron CQM1H-SCB41 Write LBA Detection Time Sequence No, Write MV Limits Sequence No

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 182
Image 182

E5jK Digital Controller Write Protocol

Appendix D

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write LBA Detection Time (Sequence No. 059)

Writes the LBA detection time.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

LBA detection time

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0003 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

LBA detection time (4 digits BCD)

0000 to 9999

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write MV at Stop Time and at PV Error (Sequence No. 060)

Writes the MV at stop time and the MV at PV error.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

MV at stop time

 

 

 

 

+3

MV at PV error

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0004 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

MV at stop time (4 digits BCD)

0000 to 1050

 

 

 

+3

MV at PV error (4 digits BCD)

0000 to 1050

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write MV Limits (Sequence No. 061)

Writes the MV upper limit, MV lower limit, and MV change rate limit.

Send Data Word Allocation (2nd Operand of PMCR)

First word of send +0

data

+1

+2

+3

+4

Number of send data words

 

 

(Undefined)

Unit No.

 

 

MV upper limit

 

MV lower limit

 

MV change rate limit

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0005 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

MV upper limit (4 digits BCD)

MV lower limit +1 to 1050

 

 

Heating/cooling control time: 0000 to 1050

 

 

 

+3

MV lower limit (4 digits BCD)

0000 to MV upper limit –1

 

 

 

+4

MV change rate limit

0000 to 1000

 

(4 digits BCD)

 

 

 

 

175

Page 182
Image 182
Omron CQM1H-SCB41 operation manual Write LBA Detection Time Sequence No, Write MV at Stop Time and at PV Error Sequence No