E5jJ Temperature Controller Protocol

Appendix G

 

 

 

Read Output Value (Sequence No. 211)

Reads the output value and stores the results in the specified word.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

storage words

+1

 

Number of receive data words

Output value

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0002

 

(4 digits BCD)

 

 

 

 

+1

Output value

0000 to 9999

 

(4 digits BCD)

When the left digit is –1, A is set and when

 

 

it is –, F is set.

Read Process Value (Sequence No. 212)

Reads the process value and status data and stores the results in the specified word.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

storage words

+1

 

 

+2

Number of receive data words

Process value

Status data

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0003

 

(4 digits BCD)

 

 

 

 

+1

Process value (4 digits BCD)

0000 to 9999

 

 

When the left digit is –1, A is set and when

 

 

it is –, F is set.

 

 

 

+2

Status data (4 digits Hex)

0000 to 9999

Read Set Point Limit (Sequence No. 213)

Reads the set point limits and stores the results in the specified word.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

send data

+1

 

Number of send data words

(Undefined)

Unit No.

 

 

239

Page 244
Image 244