IR 201

00 to 03

Port 1 Error Code (Transmission Error Status)

Transmis-

When error

Start of

 

 

When an error occurs during transmissions for a protocol

sion error

occurs

sequence

 

 

 

 

 

 

 

 

macro, an error code will be output to these bits.

 

 

 

 

 

 

0: Normal operation 1: Parity error

2: Framing error

 

 

 

 

 

 

Error codes 3 to 7 are not possible for protocol macros.

 

 

 

 

 

 

These error codes are the same regardless of the serial

 

 

 

 

 

 

communications mode.

 

 

 

 

 

 

 

IR 20104 will also turn ON except when the error code

 

 

 

 

 

 

contains all zeros. SEND&RECEIVE retry processing will

 

 

 

 

 

 

be performed for any error.

 

 

 

 

 

 

 

If communications are recovered through protocol macro

 

 

 

 

 

 

retry processing, the error code will be cleared, but will be

 

 

 

 

 

 

maintained even if a different error occurs during the retry.

 

 

 

 

 

 

 

 

 

 

 

 

 

04

Port 1 Communications Error Flag

 

 

 

 

 

 

 

This flag turns ON when an error occurs in the

 

 

 

 

 

 

communications path between the communications port

 

 

 

 

 

 

and the external device or when communications

 

 

 

 

 

 

parameters are not set correctly.

 

 

 

 

 

 

 

The operation of this flag is the same regardless of the

 

 

 

 

 

 

serial communications mode.

 

 

 

 

 

 

 

Details on the error are output as an error code to

 

 

 

 

 

 

IR 20100 to IR 20103.

 

 

 

 

 

 

 

 

 

 

 

 

 

07

Port 1 Sequence Abort Completion Flag

Sequence

When

 

 

 

 

This flag turns ON when a sequence has been aborted due

status

sequence is

 

 

 

 

to ABORT in the next process or in the error process. It will

 

aborted

 

 

 

 

 

 

 

 

 

 

be OFF if an abort has not occurred.

 

 

 

 

 

 

 

 

 

 

 

 

 

08 to 11

Port 2 Error Code (Transmission Error Status)

Transmis-

When error

 

 

 

 

Same as bits IR 20100 to IR 20103, but works together

sion error

occurs

 

 

 

 

 

 

 

 

 

 

with IR 20112.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Port 2 Communications Error Flag

 

 

 

 

 

 

 

Same as bits IR 2014, but works together with IR 20108 to

 

 

 

 

 

 

IR 20111.

 

 

 

 

 

 

 

 

 

 

 

 

 

15

Port 2 Sequence Abort Completion Flag

Sequence

When

 

 

 

 

Save as IR 20107.

 

status

sequence is

 

 

 

 

 

 

aborted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IR 202

00 to 07

Port 1 Repeat Counter PV (00 to FF hexadecimal)

Sequence

When

 

 

 

 

The repeat counter variable N is set. The value is cleared

status

repeat

 

 

 

 

 

count is

 

 

 

 

when the sequence execution starts.

 

 

 

 

 

 

 

 

refreshed

 

 

 

 

The present value N varies according to the method used

 

 

 

 

 

 

 

 

 

 

 

to initialize the value. For resets, the variable N is set to 0

 

 

 

 

 

 

when the step is started, and the step is executed accord-

 

 

 

 

 

 

ing to the set number of times. For holds, the variable N for

 

 

 

 

 

 

the present value is held when the step is started, and the

 

 

 

 

 

 

step is executed according to the set number of times.

 

 

 

 

 

 

If the Repeat Counter Setting Value is set to read word

 

 

 

 

 

 

R ( ), and 0 is read, then 0 will be stored and this step will

 

 

 

 

 

 

be skipped (the next process setting will be ignored), and

 

 

 

 

 

 

the sequence will move to the next step (+ 1). For details,

 

 

 

 

 

 

refer to the CX-Protocol Operation Manual (W344).

 

 

 

 

 

 

 

 

 

 

 

IR 203

00 to 07

Port 2 Repeat Counter PV (00 to FF hexadecimal)

 

 

 

 

 

 

Same as IR 20200 to IR 20207.

 

 

 

 

 