Chapter 10—Alarms

PowerLogic™ PM5500 series user manual

 

 

Alarms setup overview

You can use the meter display or ION Setup to configure unary, digital or standard (1-Sec) alarms. To configure logic and custom alarms, you must use ION Setup.

NOTE: If you make changes to the basic power meter setup, all alarms are disabled to prevent undesired alarm operation.

NOTICE

UNINTENDED EQUIPMENT OPERATION

After modifying any basic setup parameter:

Verify all standard alarms settings are correct and make adjustments as necessary.

Re-enable all configured alarms.

Failure to follow these instructions can result in incorrect alarm functions.

Built-in error-checking

ION Setup dynamically checks incorrect setup combinations. When you enable an alarm, you must set up the pickup and dropout limits to acceptable values first in order to exit the setup screen.

Alarm priorities

Each alarm has a priority level. Use priorities to distinguish between events that require immediate action and those that do not require action.

Alarm notification through the meter display

Alarm

 

Alarm notification and recording method

 

 

 

 

 

priority

Alarm LED1

Alarm icon

Alarm details

Alarm logging

High

Blinks while the alarm is

Blinks while the alarm is active. Alarm

Click Details to display what caused the

 

icon remains displayed until

alarm to pickup or drop off. Click Ack to

Recorded in alarm log.

active.

 

acknowledged.

acknowledge the alarm.

 

 

 

 

 

 

 

 

 

Medium

Blinks while the alarm is

Blinks while the alarm is active.

Click Details to display what caused the

Recorded in alarm log.

active.

alarm to pickup or drop off.

 

 

 

Low

Blinks while the alarm is

Blinks while the alarm is active.

Click Details to display what caused the

Recorded in alarm log.

active.

alarm to pickup or drop off..

 

 

 

None

No activity

None

None

Recorded in event log only.

 

 

 

 

 

1If the alarm / energy pulsing LED is configured for alarming.

Active alarms

When a pickup event occurs, the active alarm list appears on the meter display’s Active Alarms screen. Press “Detail” to see more event information. See “Active alarms” on page 101 for more information.

Multiple alarm considerations

If multiple alarms with different priorities are active at the same time, the display shows the alarms in the order they occurred.

Related topics

See “Monitoring” on page 56 to view the active alarms list using a web browser.