Schneider Electric HRB1684301-01 Environmental characteristics, EMC electromagnetic compatibility

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 29
Image 29

PowerLogic™ PM5500 series user manualChapter 2—Hardware reference

Electrical characteristics (Continued)

 

Number / type

4 - Externally excited digital inputs

 

 

 

 

Voltage ratings

ON state: 15 - 30 V AC / 15 - 60 V DC

 

OFF state: 0 - 6 V AC / 0 - 6 V DC

 

 

 

 

 

 

Input resistance

100 kΩ

 

 

 

Status inputs

Frequency

25 Hz maximum

 

 

Pulse width

50% duty cycle (20 ms minimum ON time)

 

 

 

 

 

Response time

10 ms

 

 

 

 

Opto Isolation

2.5 kV RMS for 60 seconds

 

 

 

 

Input burden

2 mA at 24 V AC/DC

 

2.5 mA at 60 V AC/DC

 

 

 

 

 

Environmental characteristics

Operating

Meter

-25 to 70 °C (-13 to 158 °F)

 

 

 

 

-20 to 70

°C (-4 to 158 °F). Display functions to -25 ºC

temperature

Display

 

 

(-13 °F) with reduced performance.

Storage temperature

Meter and display

-40 to 85

°C (-40 to 185 °F)

 

 

 

 

Humidity rating

 

5 to 95%

RH non-condensing at 50 °C (122 °F)

 

 

 

 

Pollution degree

 

2

 

 

 

 

Altitude

 

< 3000 m (9843 ft)

 

 

 

Location

 

Not suitable for wet locations.

 

 

 

 

EMC (electromagnetic compatibility)

Harmonic current emissions

IEC 61000-3-2

 

 

Flicker (voltage fluctuation) limits

IEC 61000-3-3

 

 

Electrostatic discharge

IEC 61000-4-2

 

 

Immunity to radiated fields

IEC 61000-4-3

 

 

Immunity to fast transients

IEC 61000-4-4

 

 

Immunity to surge

IEC 61000-4-5

 

 

Conducted immunity 150kHz to 80MHz

IEC 61000-4-6

 

 

Immunity to magnetic fields

IEC 61000-4-8

 

 

Immunity to voltage dips

IEC 61000-4-11

 

 

Immunity to damped oscillatory waves

IEC 61000-4-12

 

 

Radiated emissions

FCC part 15, EN55022 Class B

 

 

Conducted emissions

FCC part 15, EN55022 Class B

 

 

Safety

Europe

LVD compliance (EN61010-1:2010)

 

 

U.S. and Canada

cULus (UL61010-1:2012, CSA22.2 No.61010-1-12)

 

 

Protective class

Protective class II. Double insulated for user accessible

parts.

 

RS-485 communications

Number of ports

1

 

 

Maximum cable length

1219 m (4000 ft)

 

 

Unit loads

Up to 32 devices on the same bus

 

 

Parity

Even, Odd, None (1 stop bit for Odd or Even parity; 2 stop

bits for None)

 

Baud rate

9600, 19200, 38400 baud

 

 

Protocol

Modbus RTU, Modbus ASCII (7 or 8 bit), JBUS

 

 

Firmware and language file update

Update via the communication port using DLF3000

 

 

Isolation

2.5 kV RMS, double insulated

 

 

HRB1684301-01

29

Page 29
Image 29
Schneider Electric HRB1684301-01 user manual Environmental characteristics, EMC electromagnetic compatibility, Safety