Schneider Electric HRB1684301-01 Power Factor, Frequency, Total harmonic distortion, Unbalance

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 64
Image 64

Chapter 7—Viewing meter data

PowerLogic™ PM5500 series user manual

 

 

Related topics

See “Multi-tariff feature” on page 105.

Power Factor

PF True

Disp

PF

True

Disp

True power factor values per phase and total (PFa [PF1], PFb [PF2], PFc [PF3], Total), PF sign, and load type (capacitive = lead, inductive = lag).

Displacement power factor values per phase and total (PFa [PF1], PFb [PF2], PFc [PF3],, Total), PF sign, and load type (capacitive = lead, inductive = lag).

Frequency

Hz

(F)

Hz [F]

Frequency (Freq), average voltage (Vavg), average current (Iavg) and total power factor (PF) values.

Total harmonic distortion

THD

THD

thd

Amps (I)

V L-L (U)

V L-N (V)

 

 

 

Amps (I)

V L-L (U)

V L-N (V)

 

 

 

THD

THD

THD (ratio of harmonic content to the fundamental) for phase

 

 

currents (Ia [I1], Ib [I2], Ic [I3], In), line-to-line voltages(Vab [U12],

 

 

 

Amps [I], V L-L [U], V L-N [V]

Vbc [U23], Vca [U31]) and line-to-neutral voltages (Van [V1],

 

 

Vbn [V2], Vcn [V3]).

thd

thd (ratio of harmonic content to the rms value of total harmonic

 

 

content) phase currents (Ia [I1], Ib [I2], Ic [I3], In), line-to-line

 

 

 

Amps [I], V L-L [U], V L-N [V]

voltages(Vab [U12], Vbc [U23], Vca [U31]) and line-to-neutral

 

 

voltages (Van [V1], Vbn [V2], Vcn [V3]).

Related topics

See “Power quality” on page 121.

Unbalance

Unbal

Unbal

Percent unbalance readings for line-to-line voltage (V L-L [U]), line-to-neutral voltage (V L-N [V]) and current (Amps [I]).

64

HRB1684301-01

Page 64
Image 64
Schneider Electric HRB1684301-01 user manual Power Factor, Frequency, Total harmonic distortion, Unbalance