Chapter 11—Multi-tariff feature

 

 

Digital inputs are available for tariffs if they are not used, or if they are only associated with alarms (Normal). To make a digital input available, you must manually disconnect the conflicting association before configuring tariffs.

You cannot configure any digital input tariff if digital input 1 is not available for association. Likewise, digital input 2 must be available to select more than two tariffs. The status of the digital inputs is used to calculate the binary value of the active tariff, where off = 0 and on = 1. The calculation of the number of tariffs value can differ, depending on the number of digital inputs that can be selected (i.e., inputs that can be associated with multi-tariff).

To configure input mode tariffs using the front panel:

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to Meter > Tariff.

4.With the cursor pointing to Mode, press Edit.

5. Press or to change the setting to Input, then press OK.

NOTE: If a digital input association error prompt displays, you must exit from the tariff setup screens and remove the digital input association.

6. Navigate to Tariffs, then press Edit.

7. Press or to change the number of tariffs you want to set up. The maximum number of tariffs that you can apply is determined by the number of available digital inputs, as described in the table, “Digital input requirements for required number of tariffs” on page 105. Press OK.

8. Navigate to Inputs, then press Edit.

9. If applicable, press or to change how many digital inputs you want to use to control which tariff is selected (active). Press OK.

10. Press to exit, then Yes to save your changes.

Related topics

To configure the tariffs using ION Setup, see the “PM5500 series” topic in the

ION Setup online help or in the ION Setup device configuration guide, available for download at www.schneider-electric.com.