PowerLogic™ PM5500 series user manualChapter 17—MID compliance

Lock-protected setup parameters

Setup menu

Setup submenu

 

Lock-protected setup parameter

 

 

 

 

 

 

Power System

 

 

VT Connect

 

 

• VT Primary (V) and VT Secondary (V)1

 

Basic

CT on Terminal

 

CT Primary (A)

Meter

 

CT Secondary (A)

 

CT Primary Neu.(A) and CT Sec. Neu.(A)2

 

 

Sys Frequency

 

 

Phase Rotation

 

Advanced

Label

 

 

 

 

 

Tariff

Mode

 

 

 

 

HMI

User Passwords

Energy Resets

 

 

 

 

Clock

 

Date

 

 

 

 

1If using VTs (i.e., if VT Connect is set to 3VT or 2VT)

2For 3PH4W Wye Gnd systems that measure I4 current (i.e., if CT on Terminal is set to I1 I2 I3 IN)

Lock-protected functions

This section lists the meter’s lock-protected functions for MID compliance. After the meter is locked, these functions are disabled.

These functions can be accessed from the maintenance menu screen. Use the front panel buttons to navigate to the Maint > Reset menu.

Lock-protected functions

Menu

Submenu

 

Lock-protected function

 

 

 

 

 

Global Resets

Meter Initialization (all)

 

Energies

Resets

 

Single Resets

Energy

 

 

Multi-Tariff

 

 

 

 

 

 

Setting up the PM5561

You must configure all the lock-protected setup parameters before locking the meter.

When the meter is locked, those setup parameters cannot be edited.

Basic setup menu

See “Configuring basic setup parameters” on page 35 to perform basic setup.

For MID compliance, the Power System must be set to one of the following settings:

3PH4W Wye Gnd (three-phase 4-wire wye grounded)

3PH3W Dlt Ungnd (three-phase 3-wire delta ungrounded)

Advanced setup menu

See “Configuring advanced setup parameters” on page 37 to perform advanced setup.

You must use ION Setup to edit the device label.

Clock setup menu

See “Setting the clock” on page 44 to change the meter time using the display.

You can also use ION Setup to set or sync the meter time.

HRB1684301-01