PowerLogic™ PM5500 series user manualChapter 10—Alarms

Standard (1-sec) alarm setup parameters (Continued)

Setting

Option or range

Description

 

 

 

 

 

Applies to PF (power factor) alarms only. Use this set

DO Set Point Lead/Lag

Lead or Lag

the PF value and quadrant to set the dropout setpoint

for an over PF condition (PF Leading) or under PF

(Lead, Lag)

 

condition (PF Lagging). See “Power factor (PF)” on

 

 

 

 

page 91

 

 

 

Select Dig Output

None,

 

Digital Output D1,

Select the digital output(s) you want to control when the

(Outputs)

Digital Output D2,

alarm is triggered.

 

Digital Output D1 & D2

 

Setting up logic alarms

Use ION Setup to configure logic alarms.

NOTE: You must first configure the alarms you want to use as inputs to a logic alarm. For example, if you use a standard (1-Sec) alarm as one of the inputs, you must set up its setpoint pickup, dropout and delay parameters.

1.Select the logic alarm you want to set up, then click Edit.

2.Select the alarms you want to use as inputs to the logic alarm.

3.Click the double-arrow button to move the selected alarm to the Selected (max 4) box, then click OK.

4.Repeat to add more inputs to the logic alarm.

5.Configure the rest of the alarm setup parameters, click OK, then Send to save your changes to the meter.

Logic alarm setup parameters

Setting

Option or range

Description

 

 

 

 

 

See the preceding procedure. This button allows you to

Edit

select up to 4 input parameters that you want to

compare against each other. The logic alarm is set

 

 

when the result of the specified logic operation on all

 

 

inputs is true.

Enable

Yes (checked) or No

This enables or disables the alarm.

(cleared)

 

 

 

Logic Alarm 1 to Logic

ION Setup lets you modify the default label so it more

Label

clearly identifies your logic alarm. You can only use

Alarm 10 (default labels)

letters, numbers and underscores. Spaces are not

 

 

 

allowed.

 

 

 

 

AND

Output of AND operation is True only if all inputs are

 

True.

 

 

 

NAND

Output of NAND operation is True if one or more inputs

 

are False.

 

 

Type

OR

Output of OR operation is True if one or more inputs

are True.

 

 

 

NOR

Output of NOR operation is True only if all inputs are

 

False.

 

 

 

XOR

Output of XOR operation is True if only one input is

 

True, and all other inputs are False.

 

 

Priority

High, Medium, Low, None

This sets the alarm priority and notification options.

See “Alarm priorities” on page 94.

 

 

Select Dig Output

None,

 

Digital Output D1,

Select the digital output(s) you want to control when the

(Outputs)

Digital Output D2,

alarm is triggered.

 

Digital Output D1 & D2

 