Schneider Electric HRB1684301-01 Meter wiring, Power system, Direct connect voltage limits

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 20
Image 20

Chapter 2—Hardware reference

PowerLogic™ PM5500 series user manual

 

 

Meter wiring

For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com.

Wire connections to the meter’s voltage inputs, control power, digital outputs, digital (status) inputs and RS-485 communications are terminated using the supplied pluggable wire connectors.

When wiring the meter’s current inputs, terminate the wire ends with ring or split-ring crimp connectors.

Use the meter installation sheet when wiring the meter.

Connector locations

 

 

A

Voltage inputs

 

 

B

Control power

 

 

C

Ethernet ports

 

 

D

Digital outputs

 

C

E

Current inputs

 

 

 

 

F

Digital (status) inputs

G

 

G

RS-485 port

 

 

 

D

 

 

F

 

 

 

 

E

 

 

Power system

This section outlines typical requirements for wiring the voltage and current inputs of the meter to the electrical power system.

For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com.

Related topics

See “Specifications” on page 27 for voltage and current input limits.

Direct connect voltage limits

You can connect the meter’s voltage inputs directly to the phase voltage lines of the power system if the power system’s line-to-line or line-to-neutral voltages do not exceed the meter’s direct connect maximum voltage limits. The meter's voltage measurement inputs are rated by the manufacturer for up to 400 V L-N / 690 V L-L. However, the maximum voltage allowed for direct connection may be lower, depending on the local electrical codes and regulations. In US and Canada the maximum voltage on the meter voltage measurement inputs may not exceed 347 V L-N / 600 V L-L.

If your system voltage is greater than the specified direct connect maximum voltage, you must use VTs (voltage transformers) to step down the voltages.