Schneider Electric HRB1684301-01 user manual Setpoint conditions, Over setpoint

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 89
Image 89

PowerLogic™ PM5500 series user manualChapter 10—Alarms

Standard (1-Sec) alarms (Continued)

Alarm label

 

Valid range and resolution1

Units

ION Setup

Meter display

ION Setup

Meter display

 

 

 

 

 

 

Over Ground Current

Over Current, Gnd

0.000 to 99999.000

0 to 99999

A

 

 

 

 

 

Over Voltage L-L

Over Voltage, L-L

0.00 to 999999.00

0 to 999999

V

 

 

 

 

 

Under Voltage L-L

Under Voltage, L-L

0.00 to 999999.00

0 to 9999999

V

 

 

 

 

 

Over Voltage L-N

Over Voltage, L-N

0.00 to 999999.00

0 to 9999999

V

 

 

 

 

 

Under Voltage L-N

Under Voltage L-N

0.00 to 999999.00

0 to 9999999

V

 

 

 

 

 

Over Active Power

Over kW

0.0 to 9999999.0

0 to 9999999

kW

 

 

 

 

 

Over Reactive Power

Over kVAR

0.0 to 9999999.0

0 to 9999999

kVAR

 

 

 

 

 

Over Apparent Power

Over kVA

0.0 to 9999999.0

0 to 9999999

kVA

 

 

 

 

 

Leading True PF

Lead PF, True

-1.00 to -0.01 and 0.01 to 1.00

 

 

 

 

Lagging True PF

Lag PF, True

-1.00 to -0.01 and 0.01 to 1.00

 

 

 

 

Leading Disp PF

Lead PF, Disp

-1.00 to -0.01 and 0.01 to 1.00

 

 

 

 

Lagging Disp PF

Lag PF, Disp

-1.00 to -0.01 and 0.01 to 1.00

 

 

 

 

 

Over Present Active Power Demand

Over kW Dmd, Pres

0.0 to 9999999.0

0 to 9999999

kW

 

 

 

 

 

Over Last Active Power Demand

Over kW Dmd, Last

0.0 to 9999999.0

0 to 9999999

kW

 

 

 

 

 

Over Predicted Active Power Demand

Over kW Dmd, Pred

0.0 to 9999999.0

0 to 9999999

kW

 

 

 

 

 

Over Present Reactive Power Demand

Over kVAR Dmd,Pres

0.0 to 9999999.0

0 to 9999999

kVAR

 

 

 

 

 

Over Last Reactive Power Demand

Over kVAR Dmd,Last

0.0 to 9999999.0

0 to 9999999

kVAR

 

 

 

 

 

Over Predicted Reactive Power Demand

Over kVAR Dmd,Pred

0.0 to 9999999.0

0 to 9999999

kVAR

 

 

 

 

 

Over Present Apparent Power Demand

Over kVA Dmd, Pres

0.0 to 9999999.0

0 to 9999999

kVA

 

 

 

 

 

Over Last Apparent Power Demand

Over kVA Dmd, Last

0.0 to 9999999.0

0 to 9999999

kVA

 

 

 

 

 

Over Predicted Apparent Power Demand

Over kVA Dmd, Pred

0.0 to 9999999.0

0 to 9999999

kVA

 

 

 

 

 

Over Frequency

Over Frequency

0.000 to 99.000

Hz

 

 

 

 

Under Frequency

Under Frequency

0.000 to 99.000

Hz

 

 

 

 

 

Over Voltage Unbalance

Over Voltage Unbal

0.000 to 999999.000

0 to 9999999

V

 

 

 

 

 

Over Voltage THD

Over Voltage THD

0.000 to 99

%

 

 

 

 

 

Phase Loss

Phase Loss

0.00 too 999999.00

0 to 999999

 

 

 

 

 

1Some alarms use the system type and the VT or CT ratio to determine the maximum allowed setpoint. See “Maximum allowable setpoint” on page 91.

NOTE: Some alarms do not apply to all power system configurations. For example, line-to-neutral voltage alarms cannot be enabled on 3-phase delta systems.

Setpoint conditions

A setpoint condition occurs when the magnitude of the signal being monitored crosses the limit specified by the pickup setpoint setting and stays within that limit for a minimum time period specified by the pickup time delay setting.

The setpoint condition ends when the magnitude of the signal being monitored crosses the limit specified by dropout setpoint setting and stays within that limit for a minimum time period specified by dropout time delay setting.

The meter supports these types of setpoint conditions:

Over setpoint

When the value rises above the pickup setpoint setting and remains there long enough to satisfy the pickup time delay period (∆T1), the alarm condition is set to ON. When the value falls below the dropout setpoint setting and remains there long enough to satisfy the dropout time delay period (∆T2), the alarm condition is set to OFF.

HRB1684301-01

89

Page 89
Image 89
Schneider Electric HRB1684301-01 user manual Setpoint conditions, Over setpoint