PowerLogic™ PM5500 series user manual

Chapter 16—Power, energy and power factor

 

 

Power and PF lead / lag

+Q

(+kVAR)

Quadrant 2

Quadrant 1

Q (+)

PF lead

-P

(-kW)

PF lag

Q (-)

S

S

P (-)

P (+)

P (-)

P (+)

S

S

Q (+)

PF lag

+P

(+kW)

PF lead

Q (-)

 

Quadrant 3

Quadrant 4

 

 

-Q

 

 

 

(-kVAR)

 

PF lead / lag summary

 

 

 

 

 

 

Quadrant

Current phase shift

Load type

PF lead / lag

 

 

 

 

Quadrant 1

Current lags voltage

Inductive

PF lag

 

 

 

 

Quadrant 2

Current leads voltage

Capacitive

PF lead

 

 

 

 

Quadrant 3

Current lags voltage

Inductive

PF lag

 

 

 

 

Quadrant 4

Current leads voltage

Capacitive

PF lead

 

 

 

 

PF sign convention

Depending on the regional settings, the meter shows positive or negative power factor according to IEC or IEEE standards.

PF sign in IEC mode

When the regional setting is set to IEC mode, the meter correlates power factor sign (PF sign) with the direction of real power (P) flow.

For positive real power (+P), the PF sign is positive (+).

For negative real power (-P), the PF sign is negative (-).