PowerLogic™ PM5500 series user manual

Chapter 10—Alarms

 

 

LED alarm indicator

You can use the meter’s alarm / energy pulsing LED as an alarm indicator.

Location of alarm / energy pulsing LED

PM5560 / PM5561

PM5563

A Alarm / energy pulsing LED

When set to detect alarms, the LED blinks to indicate an alarm condition. See “Alarm priorities” on page 94 for a description of the LED behavior based on different alarms.

NOTE: The alarm / energy pulsing LED on the PM5561 is permanently set for energy pulsing and cannot be used for alarms.

Configuring the LED for alarms using the meter display

You can use the meter display to configure the alarm /energy pulsing LED for alarming.

Maint

Reset

 

 

 

 

 

 

Setup

Meter

 

 

 

 

 

 

Comm

 

 

 

 

 

 

Alarm

 

 

 

 

 

 

I/O

LED

D In

D Out

Inp Mtr

1.Navigate to the LED setup menu screen.

Alarm / energy pulsing LED setup parameters

Setting

Option or range

Description

 

 

 

 

 

Disabled turns off the LED completely.

Mode

Disabled, Alarm, Energy

Alarm sets the LED for alarm notification.

 

 

Energy sets the LED for energy pulsing.

 

Active Del,

 

 

Active Rec,

 

 

Active Del + Rec,

Select which accumulated energy channel to monitor and

Parameter

Reactive Del,

use for energy pulsing. This setting is ignored when the

Reactive Del + Rec,

 

LED mode is set to Alarm.

 

Apparent Del,

 

 

 

Apparent Rec,

 

 

Apparent Del + Rec

 

 

 

When configured for energy pulsing, this setting defines

Pulse Wt. (p/k_h)

1 to 9999999

how many pulses are sent to the LED for every 1 kWh,

1 kVARh or 1kVAh accumulated energy. This setting is

 

 

 

 

ignored when the LED mode is set to Alarm.

 

 

 

2.Set the mode to Alarm, then press OK.

3.Press to exit. Press Yes to save your changes.

HRB1684301-01

99

Page 99
Image 99
Schneider Electric HRB1684301-01 user manual LED alarm indicator, Configuring the LED for alarms using the meter display